beautypg.com

Siemens Simatic S7-400 User Manual

Page 475

background image

M7-400 Expansions

12-5

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Permissible Combinations

You can see from the table below which expansions can be connected to the
programmable M7-400 modules.

Table 12-1 Expansion Possibilities of the CPU 486-3, CPU 488-3, or FM 456

Programmable M7-400 Module

Slot

Slot

Slot

Slot n in the Case of Single-Width Modules

n + 1

n + 2

n + 3

Slot n and n+1

in the Case of Double-Width Modules

n + 2

n + 3

n + 4

EXM 478

EXM 478

EXM 478

EXM 478

EXM 478

EXM 478

EXM 478

EXM 478

ATM 478

EXM 478

ATM 478

ATM 478

EXM 478

ATM 478

CPU 486 3 CPU 488 3 FM 456 4

ATM 478

CPU 486-3, CPU 488-3, FM 456-4

ATM 478

ATM 478

ATM 478

ATM 478

ATM 478

MSM 478

EXM 478

MSM 478

EXM 478

EXM 478

MSM 478

EXM 478

MSM 478

ATM 478

MSM 478

ATM 478

ATM 478

MSM 478

ATM 478

Rules for the Combinations

The following rules apply for expansions from left to right after a CPU or application
module (slots n + 1, n + 2, n + 3 or n + 2, n + 3, n + 4):

1. Up to 3 EXM 478 expansion modules

2. Max. 1 MSM 478 mass storage module

(that is, always after the CPU 486-3, CPU 488-3, FM 456, or EXM 478)

3. Up to 3 ATM 478 AT adapter modules

(that is, always after the CPU 486-3, CPU 488-3, FM 456, EXM 478, or
MSM 478)

In total, a CPU or application module can be expanded with up to three modules.

This manual is related to the following products: