Interface Submodules

13-58

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Interrupts

The IF 961-CT1 can initiate an interrupt when comparison values are reached or in
the event of overflow, underflow, or zero pass of the counter.

Diagnostic Interrupt

The IF 961-CT1 can initiate a diagnostic interrupt for the following events:

Missing or incorrect counter module parameters

Hardware interrupt lost

Signal A, B, or N faulty

Which Signals Can the IF 961-CT1 Count?

The IF 961-CT1 interface submodule can count signals generated by incremental
encoders with 5 V differential signals or with 24 V signals.

The IF 961-CT1 interface submodule can also count 24 V signals generated, for
example, by a light barrier.

Additional Information

You will find more information about the interface submodule IF 961-CT1 in /108/,
IF 961-CT1 Counter Function Module, Programming and Parameter Assignment
Manual.