3 technical specifications – Siemens Simatic S7-400 User Manual
Page 511
Interface Submodules
13-15
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Interrupt Request
The interface submodule supplies an interrupt request (IRQa and IRQb) for each
serial port.
You can define the assignment of the interrupt requests IRQa and IRQb to the
appropriate processor interrupt requests in the BIOS Setup.
Table 13-14
Interrupt Assignments of the IF 962-COM Interface Submodule
Interrupt Source of the Interface Submodule
ISA Interrupt
COM a
IRQ a
Can be set in the BIOS
COM b
IRQ b
Can be set in the BIOS
setup
Default settings in the BIOS are: IRQ 4 for COM1 and IRQ3 for COM2.
Submodule ID
The IF 962-COM interface submodule has the submodule ID 41
H
.
13.4.3
Technical Specifications
Technical Specifications
The IF 962-COM interface submodule receives its supply voltage from the M7-400
programmable modules or from the M7-300/400 expansion modules. The current
consumption given in the technical specifications is the consumption required for
dimensioning the power supply, that is, the current consumption is referenced to
24 V in the M7-300 and to 5 V in the M7-400.
6ES7962-3AA00-0AC0
Technical Specifications
Supply voltage
Supplied from the M7-400
programmable modules or
from the M7-300/400
expansion modules
Current consumption in the
M7-300
(for dimensioning the 24 V
current supply)
0.04 A
Current consumption in the
M7-400
(for dimensioning the 5 V
current supply)
0.1 A
Submodule ID
41
H
Power losses
0.5 W
Dimensions
W x H x D (mm)
18.2 x 67 x 97
Weight
0.080 kg