Siemens Simatic S7-400 User Manual
Page 105
Power Supply Modules
3-25
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the PS 407 10A and the PS 407 10A R
Dimensions, Weight, and Cable Cross-Sections
Dimensions WxHxD (mm)
Weight
Cable cross-section
50x290x217
1.36 kg
3 x 1.5 mm
2
(litz wire
with wire end ferrule
with insulating collar;
use only flexible
sheath cable)
Cable diameter
3 to 9 mm
Input Rating
Input voltage
•
Rated value
•
Permitted range
110/230 VDC
120/230 VAC
88 to 300 VDC,
85 to 264 VAC
(long-range input)
System frequency
•
Rated value
•
Permitted range
50 / 60 Hz
47 to 63 Hz
Rated input current
•
At 120 VAC
•
At 110 VDC
•
At 230 VAC
•
At 230 VDC
1.2 A (0.9 A*)
1.2 A (1.0 A*)
0.6 A (0.5 A*)
0.6 A (0.5 A*)
Starting current inrush
•
At 230 VAC
Peak value 230 A,
half-value width 200
µ
s
Peak value 63 A*,
half-value width 1 ms*
•
At 300 VDC
Peak value 230 A,
half-value width 200
µ
s
Peak value 58 A*,
half-value width 1 ms
Leakage current
< 3.5 mA
Overvoltage resistance
In accordance with DIN
VDE 0160, curve W2
* PS 407 10A:
As of version 5
* PS 407 10A R:
As of version 7
Output Variables
Output voltages
•
Rated values
5.1 VDC /24 VDC
Output currents
•
Rated values
5 VDC: 10 A
24 VDC: 1.0 A
Max. residual ripple
5 VDC: 50 mV
SS
24 VDC: 200 mV
SS
Max. switching peaks
5 VDC: 150 mV
S
24 VDC: 500 mV
S
Idle conditions
5 VDC: 200 mA base
load required
24 VDC: Idling-proof
(no base load required)
Other Parameters
Protection class in accordance
with IEC 60536
I, with protective
grounding conductor
Overvoltage category
II
Pollution severity
2
Rated voltage U
e
0 < U
e
≤
50 V
150 V < U
e
≤
300 V
Test Voltage
700 VDC
(secondary <–> PE)
2300 VDC
(primary <–> PE)
Buffering of power failures:
> 20 ms
Complies with the
NAMUR
recommendation NE
21 of August 1998 at a
repeat rate of 1 s
Power input
105 W*
Power loss
29.7 W
Backup current
Max. 100
µ
A at power
off
Backup batteries (optional)
2 x Lithium AA, 3.6 V /
1.9 Ah
Protective separation
to IEC 61131-2
Yes