beautypg.com

Siemens Simatic S7-400 User Manual

Page 224

background image

Analog Modules

5-8

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Example

In the following example you can see how the positions not padded with “0” are
written for low resolution.

Table 5-4

Example: Bit Pattern of a 16-Bit and a 13-Bit Analog Value

Resolution

Analog Value

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

16-bit analog value

0

1

0

0

0

1

1

0

0

1

1

1

0

0

1

1

13-bit analog value

0

1

0

0

0

1

1

0

0

1

1

1

0

0

0

0

5.3.1

Analog Value Representation for Analog Input Channels

Introduction

The tables in this chapter contain the measured value representations for the
various measuring ranges of the analog input modules. The values in the tables
apply to all modules with the corresponding measuring ranges.

Notes for Readers of the Tables

Tables 5-6 to 5-8 contain the binary representation of the measured values.

Since the binary representation of the measured values is always the same,
starting at 5-9 these tables only contain the measured values and the units.

Measured-Value Resolution

The resolution of the analog values can differ depending on the analog module and
its parameter assignment. With resolutions < 16 bit, the bits marked with “x” are set
to “0”.

Note: This resolution doesn’t apply to temperature values. The changed
temperature values are the result of recalculation in the analog module
(see Tables 5-16 to 5-30).

This manual is related to the following products: