Analog Modules

5-54

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Compensation of the Reference Junction Temperature

There are several options for you to choose from for acquiring the reference
junction temperature in order to obtain an absolute temperature value from the
difference in temperature between the reference junction and measuring point.

You can use internal or external compensation, depending on where you want the
reference junction to be.

The last column of the following table lists the feature you must set for the
“Reference Junction” parameter in STEP 7. The reference temperature value is a
separate parameter in STEP 7.

Table 5-44 Options for Compensation of the Reference Junction Temperature

Option

Explanation

Ref.

Junction

No compensation
(refer to Figure 5-18 for connection)

When you want to acquire only the difference in
temperature between the measuring point and the
reference junction

None

Internal compensation
(refer to Figure 5-18 for connection)

If you employ internal compensation, the internal
temperature of the module is used for comparison
purposes.

Internal

External compensation with a
compensating box in leads of an
individual thermocouple
(see Figure 5-19 for connection)

You have already acquired and compensated the
reference junction temperature using a
compensating box, which you have looped into an
individual thermocouple.

No further processing is necessary owing to the
module.

None

External compensation with a
resistance thermometer to obtain
the reference junction temperature
(recommended method)
(see Figure 5-20 for connection)

You can acquire the reference temperature by
means of a resistance thermometer (pt 100) and
have it calculated by the module for any
thermocouple.

RTD on

Channel 0

External compensation with a
resistance thermometer when
thermocouples with the same
reference junction are divided
amongst several modules
(see Figure 5-20 for connection)

Use a resistance thermometer on a module that
measures the reference junction temperature. Read
in the climatic temperature value to the CPU and
transfer the value to the other modules using
SFC55.

RTD on

Channel 0

Constant reference junction
temperature (thermometer, ice bath;
see Figure 5-18 for connection)

If the reference junction temperature is constant
and known, you can specify this value in parameter
assignment in STEP 7.

Reference

temperature

value