Digital Modules

4-46

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Technical Specifications of the SM 421; DI 16

24/60 VUC

Programming package

Associated programming
package

As of STEP 7 V 2.0

Dimensions and Weight

Dimensions W H

D

(in millimeters)

25

290

210

Weight

Approx. 600 g

Data for Specific Module

Number of inputs

16

Length of cable

Unshielded
input delay

0.5 ms

3 ms

10 / 20 ms

Max. 100 m
Max. 600 m
Max. 600 m

Shielded line length

1000 m

Voltages, Currents, Potentials

Number of inputs that can be
triggered simultaneously

16

Isolation

Between channels and
backplane bus

Yes

Between the channels

Yes

In groups of

1

Permitted potential difference

Between the different
circuits

75 VDC, 60 VAC

Insulation tested with

Channels against
backplane bus and load
voltage L+

1500 VAC

Channels among one
another

1500 VAC

Current consumption

From the backplane bus

Max.150 mA

Power dissipation of the
module

Typ. 8 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

Hardware interrupt

Diagnostic Interrupt

Parameters can be
assigned
Parameters can be
assigned

Diagnostic functions

Parameters can be
assigned

Group error display

For internal fault

Red LED (INTF)

For external fault

Red LED (EXTF)

Channel error display (F)

None

Diagnostic information can
be displayed

Possible

Monitoring for

Wire break

I > 0.7 mA

Substitute value can be applied

No

Sensor Selection Data

Input voltage

Rated value

24 VUC to 60 VUC

For signal “1”

15 to 72 VDC
-15 VDC to -72 VDC
15 to 60 VAC

For signal “0”

-6 VDC to +6 VDC
0 VAC to 5 VAC

Frequency range

47 DC/AC to 63 Hz

Input current

At signal “1”

Typ. 4 mA to 10 mA

Input characteristic curve

Similar to IEC 61131

1)

Connection of two-wire BEROs

Permitted bias current

Possible
Max. 0.5 mA to 2 mA

2)

Time, Frequency

Internal preparation time for

Only hardware interrupt
enable

Max. 450

m

s

Enable hardware and
diagnostic interrupts

Max. 2 ms

Input delay

Parameters can be
assigned

Yes

Rated value

0.5/3/10/20 ms

Values go into cycle and response times.

Sensor Circuit

Resistance circuit of the sensor
for wire break monitoring

Rated voltage 24 V
(15 V to 35 V)

Rated voltage 48 V
(30 V to 60 V)

Rated voltage 60 V
(50 V to 72V)

18 k

39 k

56 k

1

) IEC 61131 does not specify any data for UC

modules. The values have been adapted as much
as possible to IEC 61131.

2)

Minimum closed-circuit current is required for wire
break monitoring.