Analog Modules

5-96

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Step Response with Strong Smoothing

The following figure illustrates the contents of Table 5-57. It shows the filter settling
time after which, in the case of a step response, the smoothed analog value is
applied to almost 100%, depending on the interference frequency suppression that
has been set. The figure applies to every change of signal at an analog input.

50

100

0

63

Interference frequency suppression 400 Hz:

60 Hz:
50 Hz:

Filter settling time in ms

Signal variation
in percent

Step response for any analog input signal

120

30

150

60

12.5

83.333 100

Figure 5-32

Step Response of the SM 431; AI 8

14 Bit (6ES7 431-1KF20-0AB0)

5.20.2

Measuring Methods and Measuring Ranges of the SM 431;
AI 8

14 Bit

Measuring Methods

You can set the following measuring methods for the input channels:

Voltage measurement

Current measurement

Resistance test

You specify the setting by means of the measuring range modules on the module
and the “Measuring Type” parameter in STEP 7.