Analog Modules

5-74

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Status, Interrupts, Diagnostics

Interrupts

None

Diagnostic functions

None

Substitute value can be applied

No

Data for Selecting a Sensor

Input range (rated values)/input
resistance

Voltage

"

1 V/200 k

W

"

10 V/200 k

W

1 V to 5 V/200 k

W

Current

"

20 mA/80

W

4 mA to 20 mA/80

W

Resistors

0 to 600

W

; of use up

to 500

W

Maximum input current for
current input (destruction limit)

40 mA continuous

Connection of the signal
sensors

For measuring voltage

Possible

For measuring current

As two-wire
transmitter

Possible; with external
transmitter supply

As four-wire
transmitter

Possible

For measuring resistance

With two-conductor
terminal

With three-conductor
terminal

Possible; cable
resistance is also
measured

With four-conductor
terminal

Possible

Characteristic linearization

No

5.18.1

Commissioning the SM 431; AI 8

13 Bit

You set the mode of operation of the SM 431; AI 8

13 Bit in STEP 7.

Parameters

You will find a description of the general procedure for assigning parameters to
analog modules in Section 5.7.

An overview of the parameters that you can set and their default settings are
shown in the table below.

Table 5-48 Parameters of the SM 431; AI 8

13 Bit

Parameter

Value Range

Default

1)

Parameter

Type

Scope

Measurement

Measuring
method

Disabled
U

Voltage

4DMU

Current (4-wire transmitter)

2DMU

Current (2-wire transmitter)

R-4L

Resistance (four-conductor
connection)

U

Static

Channel

Measuring
range

Refer to Section 5.18.2 for the measuring
ranges of the input channels that you can
set.

"

10 V

Interference
suppression

60 Hz; 50 Hz

50 Hz

1)

Only in the CC (central controller) is it possible to start up the analog modules with the default settings.