Siemens Simatic S7-400 User Manual
Page 211
Digital Modules
4-89
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 422; DO 16
20-120 VAC/2 A
Dimensions and Weight
Dimensions W
H
D
(in millimeters)
25
290
210
Weight
Approx. 800 g
Data for Specific Module
Number of outputs
16
Length of cable
•
Unshielded
•
Shielded
Max. 600 m
Max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L+
20 to 132 VAC
•
Permitted frequency range
47 Hz to 63 Hz
Total current of the outputs
Up to 40
_
C
Up to 60
_
C
With fan subassembly
Max. 16 A
24 A
Max. 7 A
16 A
Isolation
•
Between channels and
backplane bus
Yes
•
Between the channels
In groups of
Yes
1
Permitted potential difference
•
Between M
internal
and the
outputs
120 VAC
•
Between the outputs of the
different groups
250 VAC
Insulation tested with
1500 VDC
Current consumption
•
From the backplane bus
•
From load voltage L +
(without load)
Max. 600 mA
Max. 0 mA
Power dissipation of the
module
Typ. 20 W
Status, Interrupts, Diagnostics
Status display
Green LED per
channel
Interrupts
•
Diagnostic Interrupt
Parameters can be
assigned
Diagnostic functions
Parameters can be
assigned
•
Group error display
–
For internal fault
Red LED (INTF)
–
For external fault
Red LED (EXTF)
•
Diagnostic
information readable
Possible
Substitute value can be applied
Yes, programmable
Data for Selecting an Actuator
Output voltage
•
At signal “1”
L1 (–1.5 Vrms)
Output current
•
At signal “1”
Rated value
Permitted range
2 A
100 mA to 2 A
Permitted surge current
(per group)
Max. 20 A/2 cycles
•
At signal “0” (leakage
current)
Max. 2.5 mA at 30 V
Max. 4.5 mA at 132 V
Output delay (for resistive load)
•
From “ 0” to “1”
1 ms
•
At “1” to “0”
1 AC cycle
Zero cross inhibit voltage
Non-zero cross outputs
Size of the motor starter
Max. size 5 to NEMA
Lamp load
Max. 50 W
Parallel connection of 2
outputs
•
For redundant triggering of
a load
Possible (only outputs
of the same group)
•
To increase performance
Not possible
Triggering a digital input
Possible
Switch rate
•
For resistive load
Max. 10 Hz
•
For inductive load
to IEC 947-5-1, DC 13
Max. 0.5 Hz
•
For lamp load
1 Hz
Short-circuit protection of the
output
•
Min. current required for
fuse to blow
Fuse 8A/125 V 2AG
(per output)
Min. 40 A
•
Max. response time
Typ. 33 ms
Replacement fuses
•
Littelfuse
Fuse, 8 A, quick-acting
225.008