Digital Modules

4-67

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Technical Specifications of the SM 422; DO 16

20-125 VDC/1.5 A

Dimensions and Weight

Dimensions W

H

D

(in millimeters)

25

290

210

Weight

Approx. 800 g

Data for Specific Module

Number of outputs

16

Length of cable

Unshielded

Shielded

Max. 600 m

Max. 1000 m

Voltages, Currents, Potentials

Rated load voltage L1

Reverse polarity protection

20 VDC to 138 VDC

Yes, with fuse

Total current of the outputs

1)

Up to 40

_

C

Up to 60

_

C

With fan subassembly
Max. 16 A 21 A

Max. 8 A

14 A

Isolation

Between channels and
backplane bus

Yes

Between the channels

In groups of

Yes

8

Permitted potential difference

Between the outputs of the
different groups

250 VAC

Insulation tested with

1500 VAC

Current consumption

From the backplane bus

From load voltage L +
(without load)

Max. 700 mA

Max. 2 mA

Power dissipation of the
module

Typ. 10 W

Status, Interrupts, Diagnostics

Status display

Green LED per
channel

Interrupts

Diagnostic Interrupt

Parameters can be
assigned

Diagnostic functions

Parameters can be
assigned

Group error display

For internal fault

Red LED (INTF)

For external fault

Red LED (EXTF)

Diagnostic information
readable

Yes

Substitute value can be applied

Yes, programmable

Data for Selecting an Actuator

Output voltage

At signal “1”

Min. L+ (–1,0 V)

Output current

At signal “1”

Rated value

1.5 A

Permitted range

10 mA to 1.5 A

Permitted surge current

Max. 3 A
(for 10 ms)

At signal “0” (leakage
current)

Max. 0.5 mA

Output delay (for resistive load)

From “ 0” to “1”

Max. 2 ms

At “1” to “0”

Max. 13 ms

Parallel connection of 2
outputs

For redundant triggering of
a load

Possible (only outputs
of the same group)

To increase performance

Possible (only outputs
of the same group)

Triggering a digital input

Possible

Switch rate

For resistive load

Max. 10 Hz

For inductive load
to IEC 947-5-1, DC 13

Max. 0.5 Hz

Short-circuit protection
of output

Electronically
protected

2)

Threshold on

Typ. 04 A to 5 A

Replacement fuses

Fuse, 8 A/250 V, quick
blow

1) To achieve maximum performance capability,

distribute the high-current load between the two
groups.

2) To reset a deactivated output,

first set the output signal to 0 and then to 1.

If output signal 1 is written to a deactivated
output and the short circuit remains, additional
interrupts are generated (provided the diagnostic
interrupt parameter was set).