Siemens Simatic S7-400 User Manual
Page 548
Interface Submodules
13-52
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
13.7.11
Analog Value Representation for the Measuring Ranges of the
Analog Outputs
Voltage and Current Output Ranges
Table 13-44 contains the representation of
•
The voltage output range
±
10 V and
•
The current output range
±
20 mA.
Table 13-44
Representation of the Analog Output Ranges (Voltage and Current Output Ranges)
Range
Units
Output Range
Output Range
Range
Decimal
Hexadecimal
"
10 V
"
20 mA
Overflow
≥(
32512
≥(
7F00
H
11.851 V
Overrange
32496
:
27664
7EF0
H
:
6C10
H
11.7534 V
:
10.0005 V
Nominal range
27648
:
0
:
-27648
6C00
H
:
0
H
:
9400
H
10 V
:
0 V
:
-10 V
20 mA
:
0 mA
:
-20 mA
Underrange
-27664
:
-32512
93F0
H
:
8100
H
-10.0005 V
:
-11.759 V
Underflow
≤
-32528
≤(
80F0
H
-11.851 V
This manual is related to the following products: