Siemens Simatic S7-400 User Manual
Page 551
Interface Submodules
13-55
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Interference Suppression, Error Limits for
Inputs
Interference voltage
suppression for
f = n (50/60 Hz
"
1 %)
n = 1, 2, ...
•
Common-mode
interference (V
pp
< 1 V)
•
Normal-mode
interference
(Peak value of
interference < nominal
value of the input range)
Cross-talk attenuation
between the inputs
> 60 dB
0 dB
> 60 dB
Operating error limits
(in the entire temperature
range, related to the input
range)
•
Voltage input
•
Current input
Basic error limits (operating
error limits at 25
°(
C, related
to input range)
•
Voltage input
•
Current input
"
0.8 %
"
0.8 %
"
0.7 %
"
0.7 %
Linearity error (related to
input range)
"
0.05 %
Repetition accuracy (in
settled state at 25
°
C,
related to the input range)
"
0.2 %
Data for Selecting a Sensor
Input ranges (nominal
ranges)/input resistance
±
10 V/100 k
W
±
20 mA/50
W
Permissible input voltage
for voltage input
(destruction limit)
±
18 V
Permissible input current
for current input (destruc-
tion limit)
±(
40 mA
Connection of signal
sensors
•
For voltage
measurement
•
For current
measurement
Possible
As two-wire-transducer
As four-wire-transducer
•
For resistance
measurement
Possible
Possible
Possible
1)
1)
When supplied via analog outputs with a
constant current
Analog Value Generation for the Outputs
Resolution (incl. overrange)
12 bits, bipolar, twos
complement
Cycle time (all channels)
Per software
Interference Suppression, Error Limits for
Outputs
Cross-talk attenuation
between the outputs
> 60 dB
Operating error limits (over
the entire temperature
range related to the output
range)
•
Voltage output
•
Current output
"
1.0 %
"
1.0 %
Basic error limit (operating
error limits at 25
_
C, related
to output range)
•
Voltage output
•
Current output
"
0.8 %
"
0.8 %
Output ripple (related to “full
scale” of the output range;
bandwidth 50 kHz)
"
0.1 %
Data for Selecting an Actuator
Output ranges (nominal
values)
±
10 V
±
20 mA
Load impedance
•
At voltage output
•
At current output
•
With capacitive load
min. 2 kW
max. 500 W
max. 1.6 mF
Voltage output
•
Short-circuit protection
•
Short-circuit current
Yes
max. 40 mA
Current output
•
Idle voltage
max. 13.1 V
Connection of actuators
•
For voltage output
Three-wire connection
Four-wire connection
(measuring line)
•
For current output
Two-wire connection
Possible
Not possible
Possible
Status, Interrupts, Diagnostics
Interrupts
•
End-of-cycle interrupt
•
Diagnostic interrupt
Yes, can be set
Yes, can be set