4 technical specifications, 1 technical specifications of the im 467 – Siemens Simatic S7-400 User Manual
Page 410
PROFIBUS DP Master Interface IM 467/IM 467 FO
8-12
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
8.4
Technical Specifications
8.4.1
Technical Specifications of the IM 467
6ES7467-5GJ02-0AB0.
Dimensions and Weight
Dimensions
W x H x D (mm)
Weight
25 x 290 x 210
700 g
PROFIBUS DP
•
Standard
•
Transmission rate
•
Transmission
technology
PROFIBUS DP,
EN 50 170
9.6 kbps to 12 Mbps,
parameterizable in steps
RS 485 via 9-pin
subminiature D female
connector
Current consumption
Current consumption from
the S7-400 bus (24 VDC)
The IM does not consume
any current at 24 V, and it
only makes this voltage
available at the MPI/DP
interface.
Total current consumption
of the components
connected to the DP
interfaces, with a maximum
of 150 mA
PROFIBUS DP
Conditions of Use
Can be used in
SIMATIC S7-400, max. 4
IM 467 in the central
controller
IM 467 cannot be used together with the CP 443-5
Supply voltage
5 VDC via the backplane
bus
Current consumption
•
From 5 VDC
1.3 A
Addressing range
Max. 4 KB for inputs and 4
KB for outputs
DP master
Yes
•
DPV 1
No
•
Enable/disable
No
Number of connectable I/O
devices
(slaves)
96
Number of connections for
S7 functions for the
programming device and
operation and monitoring
32 + 1 diagnostic
connection
Data volume per slave
Max. 244 bytes
Consistency
Max. 128 bytes
Configuration software
STEP 7
DP slave
No
Deviations from the DP Interface Integrated
in the CPU
•
Different SSL IDs for system diagnostics
•
Possibly extended SFC run times
•
Additional return codes for SFC 14 and
SFC 15