Digital Modules

4-77

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

4.20.1

Assigning Parameters to the SM 422; DO 32

24 VDC/0.5 A

Parameter Assignment

You will find a description of the general procedure for assigning parameters to
digital modules in Section 5.7.

Parameters of the SM 422; DO 32

24 VDC/0.5 A

You will find an overview of the parameters that you can set and their default
settings for the SM 422; DO 32

24 VDC/0.5 A in the table below.

Table 4-18 Parameters of the SM 422; DO 32

24 VDC/0.5 A (6ES7422-7BL00-0AB0)

Parameter

Value Range

Default

2)

Parameter

Type

Scope

Enable

Diagnostic interrupt

1)

Yes/no

No

Dynamic

Module

Destination CPU for
interrupt

1 to 4

Static

Module

Reaction to CPU-STOP

Substitute a value (SV)
Keep last value (KLV)

SV

Dynamic

Module

Diagnostics

Wire break

No load voltage
L+/sensor supply

Short circuit to M

Short circuit to L+

Yes/no
Yes/no

Yes/no
Yes/no

No
no

No
No

Static

Channel
Channel
group

Channel
Channel

Substitute “1”

Yes/no

No

Dynamic

Channel

1)

If you use the module in ER-1/ER-2, you must set this parameter to “No” because the interrupt lines are
not available in ER-1/ER-2.

2)

Only in the CC (central controller) is it possible to start up the digital modules with the default settings.