beautypg.com

4 technical specifications – Siemens Simatic S7-400 User Manual

Page 426

background image

RS 485 Repeater

10-6

S7-400, M7-400 Programmable Controllers Module Specifications

A5E00069467-07

Amplification of the Bus Signals

The amplification of the bus signals takes place between the port for bus segment
1 or the PG/OP interface and the port for bus segment 2.

10.4

Technical Specifications

Technical Specifications of the RS 485 Repeater

Technical Specification

Power supply

pp y

Rated voltage

24 VDC

g

Ripple

20.4 to 28.8 VDC

Current consumption at rated voltage

p

g

without node at PG/OP socket

200 mA

Node at PG/OP socket (5 V/90 mA)

230 mA

Node at PG/OP socket (24 V/100 mA)

200 mA

Isolation

Yes, 500 VAC

Connection of fiber optic cables

Yes, via repeater adapters

Redundancy operation

No

Transmission rate (automatically detected by the repeater)

9.6 kbaud, 19.2 kbaud, 45.45 kbaud,
93.75 kbaud, 187.5 kbaud, 500 kbaud.
1,5 Mbaud. 3 Mbaud,
6 Mbaud, 12 Mbaud

Degree of protection

IP 20

Dimensions W

H

D (in millimeters)

45

128

67 mm

Weight (incl. packaging)

350 g

Pin Assignment of the Sub-D Connector (PG/OP Socket)

View

Pin No.

Signal Name

Designation

1

2

M24V

Ground 24 V

5

3

RxD/TxD-P

Data line B

9

4

4

RTS

Request To Send

3

8

5

M5V2

Data reference potential (from station)

3

2

7

6

P5V2

Supply plus (from station)

2

1

6

7

P24V

24 V

1

8

RxD/TxD-N

Data line A

9

This manual is related to the following products: