Terminal connection diagram, Isolation between bus segments – Siemens Simatic S7-400 User Manual
Page 425
RS 485 Repeater
10-5
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Terminal Connection Diagram
In the case of a repeater configuration with ungrounded reference potential
(ungrounded operation), any interference currents and static charges are
discharged by means of an RC network integrated in the repeater (refer to
Figure 10-1) to the protective conductor.
24 VDC
L+ M PE
M 5.2
A1
B1
A1
B1
M
22 nF
10 M
Ω
Ground bus
PE
Figure 10-1
RC Network with 10 M
Ω
for Configuration with Ungrounded Reference Potential
Isolation Between Bus Segments
Bus segment 1 and bus segment 2 are galvanically isolated from each other. The
PG/OP interface is connected internally to the port for bus segment 1. Figure 10-2
shows the front panel of the RS 485 repeater.
24 VDC
L+
M PE M 5.2
SIEMENS
RS 485-REPEATER
ON
A1
B1
A1
B1
A2
B2 A2
B2
PG
OP
DP2
OFF
ON
DP1
Terminals for bus segment 1
Terminals for bus segment 2
PG/OP
interface
Isolation
Figure 10-2
Isolation Between the Bus Segments