RS 485 Repeater

10-5

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Terminal Connection Diagram

In the case of a repeater configuration with ungrounded reference potential
(ungrounded operation), any interference currents and static charges are
discharged by means of an RC network integrated in the repeater (refer to
Figure 10-1) to the protective conductor.

24 VDC

L+ M PE

M 5.2

A1

B1

A1

B1

M

22 nF

10 M

Ground bus

PE

Figure 10-1

RC Network with 10 M

for Configuration with Ungrounded Reference Potential

Isolation Between Bus Segments

Bus segment 1 and bus segment 2 are galvanically isolated from each other. The
PG/OP interface is connected internally to the port for bus segment 1. Figure 10-2
shows the front panel of the RS 485 repeater.

24 VDC

L+

M PE M 5.2

SIEMENS

RS 485-REPEATER

ON

A1

B1

A1

B1

A2

B2 A2

B2

PG

OP

DP2

OFF

ON

DP1

Terminals for bus segment 1

Terminals for bus segment 2

PG/OP
interface

Isolation

Figure 10-2

Isolation Between the Bus Segments