Analog Modules

5-13

S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07

Analog Value Representation in Current Measuring Ranges

Table 5-12 Analog Value Representation in the Current Measuring Ranges

±

20 mA to

±

3.2 mA

System

Current Measuring Range

Dec.

Hex.

±

20 mA

±

10 mA

±

5 mA

±

3.2 mA

118.515%

32767

7FFF

23.70 mA

11.85 mA

5.93 mA

3.79 mA

Overflow

117.593%

32512

7F00

117.589%

32511

7EFF

23.52 mA

11.76 mA

5.88 mA

3.76 mA

Overrange

27649

6C01

100.000%

27648

6C00

20 mA

10 mA

5 mA

3.2 mA

75%

20736

5100

15 mA

7.5 mA

3.75 mA

2.4 mA

0.003617%

1

1

723.4 nA

361.7 nA

180.8 nA

115.7 nA

0%

0

0

0 mA

0 mA

0 mA

0 mA

Rated range

–1

FFFF

– 75%

– 20736

AF00

– 15 mA

– 7.5 mA

– 3.75 mA

– 2.4 mA

–100.000%

–27648

9400

– 20 mA

– 10 mA

– 5 mA

– 3.2 mA

–27649

93FF

Underrange

–117.593%

–32512

8100

– 23.52mA

– 11.76mA – 5.88 mA

– 3.76 mA

– 117.596%

– 32513

80FF

Underflow

– 118.519%

–32768

8000

– 23.70
mA

– 11.85
mA

– 5.93 mA

– 3.79 mA

Table 5-13 Analog Value Representation in Current Measuring Ranges 0 to 20 mA

System

Current Measuring Range

Dec.

Hex.

0 to 20 mA

118.515%

32767

7FFF

23.70 mA

Overflow

117.593%

32512

7F00

117.589%

32511

7EFF

23.52 mA

Overrange

27649

6C01

100.000%

27648

6C00

20 mA

75%

20736

5100

15 mA

0.003617%

1

1

723.4 nA

Rated range

0%

0

0

0 mA

– 1

FFFF

Underrange

– 17.593%

– 4864

ED00

– 3.52 mA

– 4865

ECFF

Underflow

v

– 17.596%

– 32768

8000