B-14 – Siemens Simatic S7-400 User Manual
Page 588
Diagnostic Data of the Signal Modules
B-14
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
B.5
Diagnostic Data of the Analog Input Modules
as of Byte 2
The structure and contents of the different bytes of the diagnostic data for the
special analog input modules are described below. The following general rule
applies: When an error occurs, the bit concerned is set to ”1”.
You will find a description of possible error causes and appropriate remedies in the
section called on the special module.
Bytes 2 and 3 of the SM 431; AI 16
16 Bit
Byte 2
7 6
0
Measuring range module incorrect or missing
Operating status 0: RUN
1: STOP
5 4 3 2 1
0
Byte 3
7 6
0
EPROM error
RAM error
ADC/DAC error
Hardware interrupt lost
5 4 3 2 1
0
0 0 0 0
0
0
0 0
Figure B-17
Bytes 2 and 3 of the Diagnostic Data of the SM 431; AI 16 x 16 Bit