beautypg.com

Message format – Yaskawa iQpump Controller Programming Manual User Manual

Page 99

background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

99

MEMOBUS / Modbus communication can perform the following operations regardless of the settings in b1-01 and b1-02:

1. Monitoring operation status of the drive
2. Setting and reading iQpump drive parameters
3. Resetting faults
4. Input multi-function commands

Important:
An OR operation is performed between the multi-function command input from the PLC and the command input from multi-function
digital input terminals S3 to S7.

Message Format

In MEMOBUS / Modbus communication, the master sends commands to the slave, and the slave responds. The message format is
configured for both sending and receiving as shown below. The length of the data packets is changed by the command (function)
contents.

Figure 89. Message Format

The space between messages must support the following:

Figure 1.90

Figure 90. Message Spacing

Slave Address

Set the iQpump drive address from 0 to 32. If 0 is selected, commands from the master will be broadcast (i.e., the iQpump drive will not
return responses).

H5-04

0428

Stopping Method
after Communication
Error
Serial Fault Sel

Selects the stopping method when a communication error is
detected.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 ~ 3

3

Programming

272

H5-05

0429

Communication
Error Detection
Selection
Serial Flt Dtct

Enables or disables the communications timeout detection function.
0: Disabled - A communications loss will NOT cause a
communications fault.
1: Enabled - If communications are lost for more than the time
specified in parameter H5-09, a communications fault will occur.

0 ~ 1

1

Programming

272

H5-06

042A

Drive Transmit Wait
Time
Transmit WaitTIM

Sets the time from when the drive receives data to when the drive
sends data.

5 ~ 65

5 ms

Programming

273

H5-07

042B

RTS Control
Selection
RTS Control Sel

Enables or disables “request to send” (RTS) control:
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when sending)

0 ~ 1

1

Programming

273

H5-09

0435

Communication
Error Detection Time
CE Detect Time

Determines how long communications must be lost before a fault is
annunciated. Works in conjunction with parameters H5-05 and
H5-04.

0 ~ 10.0

2.0 s

Programming

273

*Set H5-01 to 0 to disable drive responses to MEMOBUS / Modbus communications.

Slave address

Function code

Data

Error check

Parameter

No.

Addr. Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

Number

DDC to Drive

Drive to DDC

DDC to Drive

Command message

Response message

Command message

Time (Seconds)

24 bits long

5 ms min.

H5-06
setting

24 bits long