beautypg.com

Yaskawa iQpump Controller Programming Manual User Manual

Page 268

background image

268

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

H1-04

0403

81: Disable Sleep Mode
Function Active in Auto Mode.
Closed: Disables sleep function, Feedback Drop Detection and Over
cycle protection.
Open: Sleep function, Feedback Drop Detection and Over cycle
protection enabled.

82: Sleep Activation
Active in Auto Mode.
Closed: Drive will go to sleep (External Digital Input).
Open: No function.

0 ~ 87

84

Programming

58

H1-05

0404

Terminal S7 Function
Selection
Terminal S7 Sel

83: Thermostat Fault,
Function Active in Auto Mode.
Closed: Drive will trip on “Thermostat Fault”.
Open: Thermostat fault not active.
Open: Low Water Level Fault.
84: Pre-charge
Closed: Disables pre-charge function.
Open: Pre-charge function enabled.
85: Low Water Level

<0034>

Function Active in Auto Mode during normal operation, also used with
pre-charge function.
Function logic depends on parameter P1-15 (Water DI Config).
P1-15 = 0, or 2 (Normally open).
Closed: Low Water Level Fault.
Open: Reservoir/Tank is filled to normal level.
P1-15 = 1 or 3 (Normally Closed).
Closed: Reservoir/Tank is filled to normal level.
Pre-charge function: Function uses low water level input as “Tank /
Reservoir” feedback to indicate water level reached.
IMPORTANT
Program P1-15 to 0 or 2 when the “Low Water” function is not used.
86: Fixed Speed Auto
Function Active in Auto Mode Only, Pre-charge and Thrust Bearing
function have a higher priority. When fixed speed auto is active
(closed) drive disabled Sleep Mode and Lead / Lag operation.
Closed: Drive runs at P3-02 frequency, PI Control disabled
Open: Drive runs normal operation auto mode.
87: Thermostat Fault, Normally Closed

<0032>

Function Active in Auto Mode.
Closed: Thermostat fault not active.
Open: Drive will trip on “Thermostat Fault”.

H1-12



<0034>

87A

External Fault 3 Delay
Time
EF3 Delay Time

Sets the amount of time delay applied to the EF3 fault.
(20

≤ H1-01 ≤ 2F)

0.00 ~

300.00 s

0.00 s

Programming

H1-13



<0034>

87B

External Fault 4 Delay
Time
EF4 Delay Time

Sets the amount of time delay applied to the EF4 fault.
(20

≤ H1-02 ≤ 2F)

0.00 ~

300.00 s

0.00 s

Programming

H1-14



<0034>

87C

External Fault 5 Delay
Time
EF5 Delay Time

Sets the amount of time delay applied to the EF5 fault.
(20

≤ H1-03 ≤ 2F)

0.00 ~

300.00 s

0.00 s

Programming

H1-15



<0034>

87D

External Fault 6 Delay
Time
EF6 Delay Time

Sets the amount of time delay applied to the EF6 fault.
(20

≤ H1-04 ≤ 2F)

0.00 ~

300.00 s

0.00 s

Programming

H1-16



<0034>

87E

External Fault 7 Delay
Time
EF7 Delay Time

Sets the amount of time delay applied to the EF7 fault.
(20

≤ H1-05 ≤ 2F)

0.00 ~

300.00 s

0.00 s

Programming



Denotes that parameter can be changed when the drive is running.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.