YASKAWA TM.iQp.07 iQpump Controller Programming Manual
H1-04
0403
81: Disable Sleep Mode
Function Active in Auto Mode.
Closed: Disables sleep function, Feedback Drop Detection and Over
cycle protection.
Open: Sleep function, Feedback Drop Detection and Over cycle
protection enabled.
82: Sleep Activation
Active in Auto Mode.
Closed: Drive will go to sleep (External Digital Input).
Open: No function.
0 ~ 87
84
Programming
H1-05
0404
Terminal S7 Function
Selection
Terminal S7 Sel
83: Thermostat Fault,
Function Active in Auto Mode.
Closed: Drive will trip on “Thermostat Fault”.
Open: Thermostat fault not active.
Open: Low Water Level Fault.
84: Pre-charge
Closed: Disables pre-charge function.
Open: Pre-charge function enabled.
85: Low Water Level
<0034>
Function Active in Auto Mode during normal operation, also used with
pre-charge function.
Function logic depends on parameter P1-15 (Water DI Config).
P1-15 = 0, or 2 (Normally open).
Closed: Low Water Level Fault.
Open: Reservoir/Tank is filled to normal level.
P1-15 = 1 or 3 (Normally Closed).
Closed: Reservoir/Tank is filled to normal level.
Pre-charge function: Function uses low water level input as “Tank /
Reservoir” feedback to indicate water level reached.
IMPORTANT
Program P1-15 to 0 or 2 when the “Low Water” function is not used.
86: Fixed Speed Auto
Function Active in Auto Mode Only, Pre-charge and Thrust Bearing
function have a higher priority. When fixed speed auto is active
(closed) drive disabled Sleep Mode and Lead / Lag operation.
Closed: Drive runs at P3-02 frequency, PI Control disabled
Open: Drive runs normal operation auto mode.
87: Thermostat Fault, Normally Closed
<0032>
Function Active in Auto Mode.
Closed: Thermostat fault not active.
Open: Drive will trip on “Thermostat Fault”.
H1-12
<0034>
87A
External Fault 3 Delay
Time
EF3 Delay Time
Sets the amount of time delay applied to the EF3 fault.
(20
≤ H1-01 ≤ 2F)
0.00 ~
300.00 s
0.00 s
Programming
H1-13
<0034>
87B
External Fault 4 Delay
Time
EF4 Delay Time
Sets the amount of time delay applied to the EF4 fault.
(20
≤ H1-02 ≤ 2F)
0.00 ~
300.00 s
0.00 s
Programming
H1-14
<0034>
87C
External Fault 5 Delay
Time
EF5 Delay Time
Sets the amount of time delay applied to the EF5 fault.
(20
≤ H1-03 ≤ 2F)
0.00 ~
300.00 s
0.00 s
Programming
H1-15
<0034>
87D
External Fault 6 Delay
Time
EF6 Delay Time
Sets the amount of time delay applied to the EF6 fault.
(20
≤ H1-04 ≤ 2F)
0.00 ~
300.00 s
0.00 s
Programming
H1-16
<0034>
87E
External Fault 7 Delay
Time
EF7 Delay Time
Sets the amount of time delay applied to the EF7 fault.
(20
≤ H1-05 ≤ 2F)
0.00 ~
300.00 s
0.00 s
Programming
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page