beautypg.com

If p2-01 = “3: output speed (rpm), Figure 117. sleep function based on feedback level – Yaskawa iQpump Controller Programming Manual User Manual

Page 158

background image

158

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Figure 1.113

Figure 117. Sleep Function Based on Feedback Level

If P2-01 = “3: Output Speed (rpm)”

<0034>

The iQpump drive can be configured to enter a “sleep” condition based on the feedback signal. The drive will enter the sleep mode when
the feedback signal rises above the programmed Sleep Level (P2-02) for a time specified by the Sleep Delay Time (P2-03).

If P2-01 = “4: Low Flow (Terminal A1 - Flow meter required)”

<0034>

The iQpump drive can be configured to enter a “sleep” condition based on the feedback signal. The drive will enter the sleep mode when
the feedback signal rises above the programmed Sleep Level (P2-02) for a time specified by the Sleep Delay Time (P2-03).

Figure 1.114

Figure 118. Sleep Boost: Feedback reaches boosted setpoint

Sleep Delay Time

P2-03

Run Cmd.

PI Setpoint

Output

requency

P1-05

S-Lvl Delay Time

P2-03

Sleep Delay Time

Sleep Boost Lvl (P2-21)

PI

Feedback

PI Setpoint

Start Level (P1-04)

Sleep Boost Lvl (P2-21)

0.5 sec

P2-22

Sleep Boost Time

Sleep

Active

P2-02

Sleep Level