beautypg.com

Yaskawa iQpump Controller Programming Manual User Manual

Page 281

background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

281

P2-15

010F

No-Flow Delta Feedback
Level
NF FB Level

No-flow feedback (PID-Error: setpoint minus feedback) level used to
detect no-flow condition based on feedback value.

Delta feedback (setpoint minus feedback) has to exceed the
programmed level for the time programmed in P2-17 to detect a
no-flow condition.

0.0 ~

6000.0

(system

units

P1-02)

1.0

(system

units

P1-02)

Programming

167

P2-16

011F

No-Flow Set-point
Compensation
NF SP Comp

Set-point compensation used in the no-flow detection function.

0.0 ~

6000.0

(system

units

P1-02)

1.5

(system

units

P1-02)

Programming

167

P2-17

0120

No-Flow Feedback Delay
Time
NF Fdbk Delay Time

Delay timer used in combination with the no-flow feedback (PID-
Error: setpoint minus feedback) level (P2-15) used to detect the no-
flow condition based on the feedback value.

Delta feedback (Set-point minus feedback) has to exceed the
programmed level (P2-15) for the time programmed to detect a no-flow
condition.

0.0 ~

1000.0 s

2.0 s

Programming

168

P2-18

0121

No-Flow Motor RPM
Sample Time
NF RPM Sample Tm

No-flow detection motor rpm sample rate.

0.1 ~

1000.0 s

2.0 s

Programming

168

P2-19

0122

No-Flow Feedback
Detection Direction
NF Fdbk Det Direct

Direction of feedback detection upon return of no-flow detection.
0: Outside Bandwidth (P2-15)
1: Inside Bandwidth (P2-15)

0 ~ 1

0

Programming

168

P2-20



0123

Alternative Sleep
Activate Level
SLP Act Level

When P2-01 Sleep Level Type is set for 0 (Output Frequency) or 3
(Output Speed), the sleep function becomes active when the output
frequency is greater or equal to the level in P2-20. When programmed
to 0, the sleep function will become active above the P2-02 Sleep.

Level.Display Units for Sleep Activate Level P2-20 when P2-01 is
programmed for the following:

<0034>

P2-01=0: Display based on “Hz”
P2-01=1: Display based on “Hz”
P2-01=2: Display based on “Hz”
P2-01=3: Display based on “rpm”
P2-01=4: Display based on “Hz”

A value of 0 disables this function.

0.0 ~

6000.0

0.0

Programming

168

P2-21

<0034>

820

Sleep Boost Level
Sleep Boost Lvl

Sets the amount of boost applied to the setpoint just before going to
sleep. A setting of 0.0 disables the sleep boost function. (Internally
limited to 25 % of P1-03.)

0.0 ~

6000.0

(system

units

P1-02)

0.0

Programming

P2-22

<0034>

821

Sleep Boost Maximum
Time
Sleep Boost Time

Sets the amount of time the system (feedback) has to reach the
“boosted” setpoint. If more than this time elapses, the drive will go to
sleep

1.0 ~

160.0 s

5.0 s

Programming

P2-23



<0034>

822

Anti-No-Flow
Bandwidth
ANF Bandwidth

Sets the amount of PI “Error” bandwidth used to detect the no-flow
condition.
Operation can become less stable if this value is set too high. A setting
of 0.00 % disables this feature.

0.00 ~

2.00 %

0.40 %

Programming

P2-24



<0034>

823

Anti-No-Flow Detection
Time
ANF Det Time

Sets the time delay after no-flow is detected before the drive starts its
increased deceleration rate.

1.0 ~

60.0 s

10.0 s

Programming

P2-25



<0034>

824

Anti-No-Flow Release
Level
ANF Release Lvl

Once the Anti-No-Flow activates (after the P2-24 time), the feedback
must drop this amount below the setpoint for the Anti-No-Flow to
disengage and return to normal PI operation.

0.0 ~

100.0 psi

3.0 psi

Programming



Denotes that parameter can be changed when the drive is running.

Pump Multiplex

P3-01

0614

Lead-Lag Control
Lead-Lag Control

Selects lead-lag detection operation.

0: Output Frequency (Output Frequency). 0: Uses P3-02, P3-04, P3-06,
P3-09, P3-10.
1: Feedback (Feedback Level). 1: Uses P3-03, P3-04, P3-05, P3-06.
2: Feedback + Fout (Feedback Level and Output Frequency). 2: Uses
P3-02, P3-03, P3-05, P3-06, P3-07, P3-08, P3-10.

Works in conjunction with parameters P2-11 to P2-19.

0 ~ 2

0

Programming

172

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.