H4 Analog Outputs

H4-01 Terminal FM Monitor Selection

Setting Range:

1 ~ 53

Factory Default: 2: Output Freq

The FM and AM analog output terminals can be programmed to output a 0-10 Vdc signal proportional to any one of functions detailed in

Table 33 on page 93

.

Table 33

When the H4-01 or H4-04 are configured the iQpump drive will output 10 Vdc to represent 100% of the function programmed into them.

Figure 1.84

Figure 83. Analog Output Signal Level as a Function of the Monitor Value

Function: Frequency Ref (Setting: 1)

The analog output level will correspond to the chosen Speed Command input whether it is input via the digital operator, analog input, or
serial communication. 100% will be equivalent to the maximum output frequency of the iQpump drive (E1-04).

Function: Output Freq (Setting: 2)

The analog output level will correspond to the actual Speed being output by the iQpump drive and will include the acceleration and
deceleration ramps. 100% will be equivalent to the maximum output frequency of the iQpump drive (E1-04).

Function: Output Current (Setting: 3)

The analog output level will correspond to the output current level of the drive. 100% will be equivalent to the drives rated output current
which is based on the kVA Rating of the iQpump drive (o2-04).

Function: Output Voltage (Setting: 6)

The analog output level will correspond to the output voltage level of the drive. 100% will be equivalent to either 200 Vac or 400 Vac
depending on the input voltage rating of the drive.

Setting

Description

Setting

Description

1

Frequency Ref

20

SFS Output*

2

Output Freq

24

PI Feedback

3

Output Current

31

Not Used

6

Output Voltage

36

PI Input

7

DC Bus Voltage

37

PI Output

8

Output kWatts

38

PI Setpoint

15

Term A1 Level

51

Auto Mode Fref

16

Term A2 Level

52

Hand Mode Fref

18

Mot SEC Current

53

PI Feedback 2

* SFS is the internal soft starter signal. This signal is generated from the reference and often it passes through the accel / decel functions.

10 V

100%

0

Out

put

V

ol

tage

Monitor

Function Level