H4 analog outputs, H4-01 terminal fm monitor selection, Function: frequency ref (setting: 1) – Yaskawa iQpump Controller Programming Manual User Manual
Page 93: Function: output freq (setting: 2), Function: output current (setting: 3), Function: output voltage (setting: 6)
YASKAWA TM.iQp.07 iQpump Controller Programming Manual
93
H4 Analog Outputs
◆
H4-01 Terminal FM Monitor Selection
Setting Range:
1 ~ 53
Factory Default: 2: Output Freq
The FM and AM analog output terminals can be programmed to output a 0-10 Vdc signal proportional to any one of functions detailed in
Table 33
When the H4-01 or H4-04 are configured the iQpump drive will output 10 Vdc to represent 100% of the function programmed into them.
Figure 1.84
Figure 83. Analog Output Signal Level as a Function of the Monitor Value
■
Function: Frequency Ref (Setting: 1)
The analog output level will correspond to the chosen Speed Command input whether it is input via the digital operator, analog input, or
serial communication. 100% will be equivalent to the maximum output frequency of the iQpump drive (E1-04).
■
Function: Output Freq (Setting: 2)
The analog output level will correspond to the actual Speed being output by the iQpump drive and will include the acceleration and
deceleration ramps. 100% will be equivalent to the maximum output frequency of the iQpump drive (E1-04).
■
Function: Output Current (Setting: 3)
The analog output level will correspond to the output current level of the drive. 100% will be equivalent to the drives rated output current
which is based on the kVA Rating of the iQpump drive (o2-04).
■
Function: Output Voltage (Setting: 6)
The analog output level will correspond to the output voltage level of the drive. 100% will be equivalent to either 200 Vac or 400 Vac
depending on the input voltage rating of the drive.
Setting
Description
Setting
Description
1
Frequency Ref
20
SFS Output*
2
Output Freq
24
PI Feedback
3
Output Current
31
Not Used
6
Output Voltage
36
PI Input
7
DC Bus Voltage
37
PI Output
8
Output kWatts
38
PI Setpoint
15
Term A1 Level
51
Auto Mode Fref
16
Term A2 Level
52
Hand Mode Fref
18
Mot SEC Current
53
PI Feedback 2
* SFS is the internal soft starter signal. This signal is generated from the reference and often it passes through the accel / decel functions.
10 V
100%
0
Out
put
V
ol
tage
Monitor
Function Level