U1-16
004F
Terminal A2 Input Voltage
Term A2 level
Displays the input current (or voltage) on Terminal A2, as a percentage of 20 mA (or 10 Vdc).
U1-18
0051
Motor Secondary Current (Iq)
Mot SEC Current
Displays the amount of current being used by the motor to produce torque (Iq).
U1-20
0053
Output Frequency After Soft
Start
SFS Output
Displays the frequency reference (speed command) after the accel and decel ramps.
U1-24
0057
PI Feedback Value
PI Feedback
Displays the feedback signal when PI control is used.
U1-28
005B
CPU Number
CPU ID
Displays control board hardware revision.
U1-29
005C
kWh
kWh Lo 4 Digits
Displays the accumulated kWh.
U1-30
005D
MWh
kWh Hi 5 Digits
Displays the accumulated MWh.
U1-34
0061
First Parameter Causing an OPE
OPE Detected
Displays the parameter number causing an “OPE” fault.
U1-36
0063
PI Input
PI Input
Displays the “error” in the PI regulator. (U1-36 = PI Set-point - PI Feedback).
U1-37
0064
PI Output
PI Output
Displays the output of the PI as a percentage of maximum frequency (E1-04).
U1-38
0065
PI Set-point
PI Set-point
Displays the setpoint of the PI regulator (U1-38 = PI reference + PI bias).
U1-39
0066
Memobus Communication Error
Code
Transmit Err
U1-40
0067
Heatsink Cooling Fan Operation
Time
FAN Elapsed Time
Displays total operating time of the heatsink cooling fan.
U1-62
007D
Running Queue No
Running Queue No
Position in the iQpump Memobus Multiplex Running Queue
U1-67
009B
Network Activity
Network Activity
Shows network traffic. A fluctuating number from 0 to 1000 denotes activity, while a
relatively constant 0 denotes no activity.
Unit changes based on network status:
<->: Drive can not communicate to other drives
<+>: Drive is a Node on a network
U1-68
0009C
Time to Alternate
Time to Alternate
Time remaining before a drive requests alternation which is dependent on P9-04.
U1-90
0720
Pump Set-point
Pump Set-point
Displays drive setpoint.
Resolution 0.1
Note:
Does not include setpoint compensation (U1-93).
U1-91
0721
Pump Feedback
Pump Feedback
Displays scaled feedback.
Resolution 0.1
Parameter No.
Addr.
Hex
Parameter Name Digital
Operator Display
Description
Monitor
1: CRC error
1: Data length error
Not used. Always 0.
1: Parity error
1: Overrun error
1: Framing error
1: Timeover
Not used. Always 0
.
0 0 0 0 0 0 0 0