o2-06 Operation Selection when Digital Operator is Disconnected
Leaving o2-06 enabled will cause the iQpump drive to fault, when the digital operator is removed, even if it’s not outputting to the motor.
The reset key on the digital operator will need to be pressed after reconnecting the digital operator to reset the fault and continue normal
operation.
If o2-06 = “0: Disabled” then the iQpump drive will not fault if the digital operator is disconnected, but the iQpump drive will discontinue
motor operation. If full iQpump drive operation is required while the digital operator is removed set o2-06 = “0: Disabled” and o2-15 =
“0: Disabled” (Hand Key Function). If both o2-06 and o2-15 are disabled then the digital operator can be disconnected without disturbing
iQpump drive operation.
◆
o2-07 Cumulative Operating Time Setting
Setting Range:
0 ~ 65535 Hours
Factory Default: 0 Hours
Refer to parameter o2-07 in Appendix A for description details.
◆
o2-08 Cumulative Operation Time Selection
The iQpump drive features an Elapsed Timer monitor that records in units of hours. The Elapsed Timer monitor is U1-13. Parameter o2-
08 programs this function to either accumulate elapsed hours based on time the iQpump drive is powered (o2-08 = “0: Power-On Time”)
or time the iQpump drive is running (o2-08 = “1: Running Time”). The iQpump drive is considered “running” anytime there is an active
run command or when the iQpump drive is outputting voltage (i.e. including during deceleration).
Parameter o2-07 allows manual adjustment of the Elapsed Timer, primarily to accommodate maintenance or control board replacement in
the event of damage. To reset the Elapsed Timer back to zero, set o2-07 = 0.
◆
o2-10 Cumulative Cooling Fan Operation Time Setting
Setting Range:
0 ~ 65535 hr
Factory Default: 0 hr
The elapsed time of heatsink cooling fan operation is tracked by the U1-40 monitor. Much like the o2-07 parameter can be used to adjust
or reset the iQpump drive operation elapsed timer, parameter o2-10 can be used to adjust the time displayed by the U1-40 monitor in the
event of fan replacement.
Setting
Description
0
Disabled
1
Enabled (
factory default
)
Setting
Description
0
Power-On Time
1
Running Time (
factory default
)
-DRIVE-
Elapsed Time
U1-13 = 0H
U1-14 =
U1-15 =
03010
34.1%
-DRIVE-
FAN Elapsed Time
U1-40 = 152H
U1-51 =
U1-52 =
52.33%
57.60%
Rdy