Yaskawa iQpump Controller Programming Manual User Manual
Page 214

214
YASKAWA
TM.iQp.07 iQpump Controller Programming Manual
Table 89 Related Parameters
<0034>
P2-02
060B
Sleep Level
Sleep Level
Sleep activates when selected level (P2-01) reaches programmed
sleep level for time specified in P2-03. The level type is determined
by P2-01. This function is only active during running while operating
in auto mode.
If P1-01 = 3, the function is active when there is only one drive
running on the network.
<0034>
Display Units for Sleep Level P2-02 when P2-01 is programmed for
the following:
P2-01=0: Display based on “Hz”
P2-01=1: Display based on “A”
P2-01=2: Display based on P1-02 Selection
P2-01=3: Display based on “rpm”
<0034>
P2-01=4: Display based on P6-02 Selection
<0034>
Note:
When P2-01 is set for a value of 2, display units will be
dependent on P1-02 setting. If P2-02 = 0, pump will sleep at
minimum speed.
0.0 ~
6000.0
0.0
Programming
P2-03
060C
Sleep Delay Time
Sleep Delay Time
Delay time before drive enters sleep mode when criteria is met as
defined by parameter P2-02.
0 ~ 3600
5 s
Programming
P2-20
0123
Alternative Sleep Activate Level
SLP Act. Level
When P2-01 Sleep Level Type is set for 0 (Output Frequency) or 3
(Output Speed), the sleep function becomes active when the output
frequency is greater or equal to the level in P2-20. When
programmed to 0, the sleep function will become active above the
P2-02 Sleep Level.
Display Units for Sleep Activate Level P2-20 when P2-01 is
programmed for the following:
<0034>
P2-01=0: Display based on “Hz”
P2-01=1: Display based on “Hz”
P2-01=2: Display based on “Hz”
P2-01=3: Display based on “rpm”
P2-01=4: Display based on “Hz”
A value of 0 disables this function.
0.0 ~
6000.0
0.0
Programming
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
P6-01
840
Flow Meter Scaling
Flow Meter Scale
Sets the scaling for the flow meter connected to terminal A1. Enter
the gal / min when the flow meter is at it's rated output. A setting of
0.0 disables all flow meter functions.
0.0 ~
6000.0
Gpm
0.0 Gpm Programming
P6-02
841
Water Flow Units
Water Flow Units
Sets the units displayed for monitor U1-95. Also sets units for
parameters P2-02 and P6-04.
0: U.S. Gallons / min (GPM)
1: U.S. Gallons / hr (GPH)
2: U.S. Barrels / min (BPM)
3: U.S. Barrels / hr (BPH)
4: U.S. Barrels / day (BPD)
0 ~ 4
0
Programming
P6-03
842
Flow Accumulation Reset
Flow Accum Reset
Resets the accumulated flow and returns the monitors U1-96 and
U1-97 to zero.
0: No Reset
7770: Reset Accum.All other settings will have no effect
NOTE:
After this parameter is changed it will automatically return to
a “0”.
0 ~ 65535
0
Programming
P6-04
843
Low Flow Level
Low Flow Level
If the drive is running, and the flow goes below this level for more
than the P6-05 time, a Low Flow fault or alarm will occur. A setting
of 0 disables the low flow detection.
0.0 ~
6000.0
(*n1)
0.0
Programming
P6-05
844
Low Flow Detection Delay Time
When Already Running
Low Flow Tim Run
Sets the amount of time the flow rate must be below the P6-04 level
before a Low Flow condition is detected
0.0 ~
6000.0 s
10
Programming
P6-06
845
Low Flow Detection Wait Time
At Start
Low Flow Time St
Sets the time the drive will wait after coming out of a zero speed
condition before activating Low Flow detection.
0.0 ~
3600.0 min
0.0
Programming
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location