B1-02 = 1 auto mode start – Yaskawa iQpump Controller Programming Manual User Manual
Page 18
![background image](https://www.manualsdir.com/files/819854/content/doc018.png)
18
YASKAWA
TM.iQp.07 iQpump Controller Programming Manual
Figure 1.8
Figure 8. Connection Diagram of External Start / Stop Switch
b1-02 = 2, Serial Com
If the Run command is determined by Serial Communication:“b1-02 = 2: Serial Communications,” and initiate the Run command
through the serial communications. Refer to
(in the previous b1 sequence section) for the connection diagram for serial
communications through the RS232 / 485 terminals to R+, R-, S+ and S-. The following is a simple setup procedure for programming the
iQpump drive and PC Serial communications to initiate Run and Stop commands through serial communications.
1. Program b1-02 = “2: Serial communications”.
2. Program the following H5 parameters:
H5-01 Serial Communication Address: 31
H5-02 Serial Baud Rate: 9600 Baud (setting 3).
H5-03: Serial Communication Parity Selection: None (setting 0)
3. Initiate a Start / Stop command
iQpump command register number: 0001
Stop Command: Transmit value of 0000 (16 bit) to iQpump command address.
Start Command: Transmit value of 0001 (16 bit) to iQpump command address.
Reset Command: Transmit value of 0008 (16 bit) to iQpump command address.
b1-02 = 3, Option PCB
If the Run command input is determined by a network communications option PCB: “b1-02 = 3: Option PCB,” and initiate the Run
command through the available network communications option PCB listed below. The Installation Guides (IG) and Technical Manuals
(TM) are available at http://iQpump.yaskawa.com.
The iQpump Controller allows for monitoring, diagnostics and control using any of the following communication option cards:
Note: Refer to the communication card instruction manual or consult factory for installation and operation instructions.
b1-02 = 5, Timed Run
If the Run command input is determined by a Timed Run: “b1-02 = 5: Timed Run,” when this feature is enabled, the drive will run at
the HAND frequency reference for the time specified in parameter P4-18. Timed Run cannot be enabled when in multiplex mode
(P1-01 > 0).
Profibus DP Option Card CM061
Manual: IG.AFD.12
DeviceNet Option Card CM05X
Manual: IG.AFD.14
Modbus Plus Option Card CM071
Manual: IG.AFD.17
Modbus TCP / IP Option Card CM090
Manual: IG.AFD.25
EtherNet / IP Option Card CM092
Manual: IG.AFD.26
b
b1-02 = 1
Auto Mode Start
External Switch or
Relay Contact
S1
S2
S3 (H1-01)
S4 (H1-02)
S5 (H1-03)
S6 (H1-04)
S7 (H1-05)
SN
SC
SP 24 VDC +/- 20%, 8 mA
E (G)