B1-07 local / remote run selection, B1-08 run command selection during programming, Figure 17. coast to stop with timer – Yaskawa iQpump Controller Programming Manual User Manual

Page 23

background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

23

Figure 1.16

Figure 16. DC Injection Braking to Stop

Important: If an overcurrent (OC) fault occurs during DCInj to Stop, lengthen the Minimum Baseblock Time (L2-03) until the fault no
longer occurs.

3: Coast w / Timer: When the Run command is removed, the iQpump drive will turn off its output and the motor will coast to a stop. If
a Run command is input before time T (operation wait time) expires, the iQpump drive will not run and the Run command will need to be
cycled before operation can occur. The time T (operation wait time) is determined by the output frequency when the Run command is
removed and the active deceleration time (C1-02).

Figure 1.17

Figure 17. Coast to Stop with Timer

b1-07 Local / Remote Run Selection

Note: Used with LCD Operator only.

b1-08 Run Command Selection During Programming

As a safety precaution, the iQpump drive will not normally respond to a Run input when the digital operator is being used to adjust
parameters. If it is necessary that external Run commands be recognized even while the drive is being programmed, set b1-08 = “1:
Enabled.”

Setting

Description

0

Cycle External Run - If the run command is closed when switching from Hand (local) mode to Auto (remote) mode, the drive will not run.
(

factory default

)

1

Accept External Run - If the run command is closed when switching from Hand (local) mode to Auto (remote) mode, the drive WILL run.

Setting

Description

0

Disabled (

factory default

)

1

Enabled

ON

OFF

Run Command

Output Frequency

Drive Output Voltage Interrupted

DC Injection Brake

DC Injection Brake Time

Minimum Baseblock

Time (L2-03)

100 %

0 %

D

C

In

je

ct

io

n Br

ak

e

T

im

e

b2-04 x 10

b2-04

10%

100% (Maximum

Output Frequency)

b2-04

(CLOSED)

(OPEN)

Run Command

Output Frequency

Drive Output

Voltage

Interrupted

OFF

ON

Timer Value T

(C1-02)

100 %

0 %

O

pe

ra

tio

n W

a

it T

im

e (

T

)

Deceleration

Time (C1-02)

Minimum

Baseblock

Time (L2-03)

Minimum

Output

Frequency

100% (Maximum

Output

Frequency)

Output Frequency at Stop Command Input

Ignored

Run Command

Timer Value T

(OPEN)

(CLOSED)