B1-07 local / remote run selection, B1-08 run command selection during programming, Figure 17. coast to stop with timer – Yaskawa iQpump Controller Programming Manual User Manual
Page 23
YASKAWA TM.iQp.07 iQpump Controller Programming Manual
23
Figure 1.16
Figure 16. DC Injection Braking to Stop
Important: If an overcurrent (OC) fault occurs during DCInj to Stop, lengthen the Minimum Baseblock Time (L2-03) until the fault no
longer occurs.
3: Coast w / Timer: When the Run command is removed, the iQpump drive will turn off its output and the motor will coast to a stop. If
a Run command is input before time T (operation wait time) expires, the iQpump drive will not run and the Run command will need to be
cycled before operation can occur. The time T (operation wait time) is determined by the output frequency when the Run command is
removed and the active deceleration time (C1-02).
Figure 1.17
Figure 17. Coast to Stop with Timer
◆
b1-07 Local / Remote Run Selection
Note: Used with LCD Operator only.
◆
b1-08 Run Command Selection During Programming
As a safety precaution, the iQpump drive will not normally respond to a Run input when the digital operator is being used to adjust
parameters. If it is necessary that external Run commands be recognized even while the drive is being programmed, set b1-08 = “1:
Enabled.”
Setting
Description
0
Cycle External Run - If the run command is closed when switching from Hand (local) mode to Auto (remote) mode, the drive will not run.
(
factory default
)
1
Accept External Run - If the run command is closed when switching from Hand (local) mode to Auto (remote) mode, the drive WILL run.
Setting
Description
0
Disabled (
factory default
)
1
Enabled
ON
OFF
Run Command
Output Frequency
Drive Output Voltage Interrupted
DC Injection Brake
DC Injection Brake Time
Minimum Baseblock
Time (L2-03)
100 %
0 %
D
C
In
je
ct
io
n Br
ak
e
T
im
e
b2-04 x 10
b2-04
10%
100% (Maximum
Output Frequency)
b2-04
(CLOSED)
(OPEN)
Run Command
Output Frequency
Drive Output
Voltage
Interrupted
OFF
ON
Timer Value T
(C1-02)
100 %
0 %
O
pe
ra
tio
n W
a
it T
im
e (
T
)
Deceleration
Time (C1-02)
Minimum
Baseblock
Time (L2-03)
Minimum
Output
Frequency
100% (Maximum
Output
Frequency)
Output Frequency at Stop Command Input
Ignored
Run Command
Timer Value T
(OPEN)
(CLOSED)