Yaskawa iQpump Controller Programming Manual User Manual
Page 239
YASKAWA TM.iQp.07 iQpump Controller Programming Manual
239
Table 116 Monitors
Monitor shown only when P1-01 = 3 (MEMOBUS / Modbus Network)
◆
P9-05 Lag Drive Mode
◆
P9-06 Lag Fixed Speed
Setting Range:
0.00 ~ 120.00 Hz
Factory Default: 55.00 Hz
Refer to parameter P9-06 in Appendix A for description details.
◆
P9-07 Lag Fixed Speed Delay
Setting Range:
0.0 ~ 1000 s
Factory Default: 5 s
Refer to parameter P9-07 in Appendix A for description details.
◆
P9-08 Add Pump Mode
◆
P9-09 Add Freq Level
Setting Range:
0.0 ~ 120.0 Hz
Factory Default: 56.0 Hz
Refer to parameter P9-09 in Appendix A for description details.
◆
P9-10 Add Delta Level
Setting Range:
0 ~ 6000.0
Factory Default: 5.0
Refer to parameter P9-10 in Appendix A for description details.
◆
P9-11 Add Delay Time
Setting Range:
0 ~ 3600 s
Factory Default: 10 s
Refer to parameter P9-11 in Appendix A for description details.
Monitor
No.
Addr.
Hex
Monitor Name
Digital Operator Display
Description
U1-68
0009C
Time to Alternate
Time to Alternate
Time remaining before a drive requests alternation which is dependent on P9-04.
Setting
Description
0
Fixed Speed - Runs at the P9-06 setting.
1
PI Regulation - Uses PI to determine speed.
Setting
Description
0
Output Frequency
1
Feedback
2
Feedback + Fout