Yaskawa iQpump Controller Programming Manual User Manual
Page 271
YASKAWA TM.iQp.07 iQpump Controller Programming Manual
271
H2-02
(continued)
040C
Terminal M3-M4
Function Selection
Term M3-M4 Sel
55: Lube Pump
<0034>
Closed: When the Lube Pump Feature is active.
This will energize for the time set in parameter P4-23 each time the
drive is supposed to start. The drive will delay starting for the P4-23
time.
56: High Flow
<0034>
Closed: During the “High Flow Fault” condition. -OR-
Closed: During a high flow condition as set by P6-12 ~ P6-14
(included “High Flow Alarm”)
57: Low Water Level
<0034>
Closed: During the “Low Water Level” condition as set by P8-07 and
P8-08. -OR-
Closed: During the LOWWL - Low Water Level Fault”.
This will energize if the level in the well drops below the Low Level
Detection Level (P8-07) for more than the Low Level Detection Delay
Time (P8-08), or if there is a LOWWL - Low Water Level Fault.
0 ~ 57
41
Programming
Analog Inputs
H3-02
0411
Terminal A1 Gain Setting
Terminal A1 Gain
Sets the speed command when 10 V is input, as a percentage of the
maximum output frequency (E1-04).
0.0 ~
1000.0 %
100.0 % Programming
H3-03
0412
Terminal A1 Bias Setting
Terminal A1 Bias
Sets the speed command when 0 V is input, as a percentage of the
maximum output frequency (E1-04).
–100.0 ~
+100.0 %
0.0 %
Programming
H3-08
0417
Terminal A2 Signal
Level Selection
Term A2 Signal
Selects the signal level of Terminal A2.
0: 0 - 10 Vdc (switch S1-2 must be in the off position)
2: 4 - 20 mA (switch S1-2 must be in the on position)
3: 0- 20 mA
0 or 2
2
Programming
H3-09
0418
Aux Terminal Function
Selection
Terminal A2 Sel
Selects what effect the aux terminal has on the drive.
0: Frequency Bias - 0 - 100 % bias
2: Aux Reference
B: PI Feedback
D: Frequency Bias 2 - 0 - 100 % bias
E: Motor Temperature - See parameters L1-03 & L1-04
16: PI Differential
1F: Not Used
0 ~ 1F
B
Programming
H3-10
0419
Terminal A2 Gain Setting
Terminal A2 Gain
Sets the percentage when 10 V (20 mA) is input.
0.0 ~
1000.0 %
100.0 % Programming
H3-11
041A
Terminal A2 Bias Setting
Terminal A2 Bias
Sets the percentage when 0 V (4 mA) is input.
–100.0 ~
+100.0 %
0.0 %
Programming
H3-12
041B
Analog Input Filter Time
Constant Filter Avg Time
Analog Input Fil Tim
Used to “smooth” out erratic or noisy analog input signals.
0.00 ~
2.00 s
0.30 s
Programming
H3-13
041C
Master Frequency
Reference
Terminal Sel TA1/A2
Select
Determines which terminal will be the main reference source.
0: Main Fref TA1 - Terminal TA1 is the main speed command and
Terminal TA2 is the Aux speed command.
1: Main Fref TA2 - Terminal TA2 is the main speed command and
Terminal TA1 is the Aux speed command. Only effective when H3-09
is set to 2 “Aux Reference”.
0 ~ 1
0
Programming
Denotes that parameter can be changed when the drive is running.
Analog Outputs
H4-01
041D
Terminal FM Monitor
Selection
Terminal FM Sel
Selects which monitor will be output on Terminals FM and AC.
1: Frequency Ref (100 % = max. output frequency)
2: Output Freq (100 % = max. output frequency)
3: Output Current (100 % = drive rated current)
6: Output Voltage (100 % = 230 V or 100 % = 460 V)
7: DC Bus Voltage (100 % = 400 V or 100 % = 800 V)
8: Output kWatts (100 % = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100 % = Motor rated secondary current)
20: SFS Output (100 % = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Set-point
Note:
100% = 10 V DC output x FM gain setting (H4-02).
1 ~ 38
<0032>
2
Programming
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.