YASKAWA TM.iQp.07 iQpump Controller Programming Manual

271

H2-02

(continued)

040C

Terminal M3-M4
Function Selection
Term M3-M4 Sel

55: Lube Pump

<0034>

Closed: When the Lube Pump Feature is active.
This will energize for the time set in parameter P4-23 each time the
drive is supposed to start. The drive will delay starting for the P4-23
time.
56: High Flow

<0034>

Closed: During the “High Flow Fault” condition. -OR-
Closed: During a high flow condition as set by P6-12 ~ P6-14
(included “High Flow Alarm”)
57: Low Water Level

<0034>

Closed: During the “Low Water Level” condition as set by P8-07 and
P8-08. -OR-
Closed: During the LOWWL - Low Water Level Fault”.
This will energize if the level in the well drops below the Low Level
Detection Level (P8-07) for more than the Low Level Detection Delay
Time (P8-08), or if there is a LOWWL - Low Water Level Fault.

0 ~ 57

41

Programming

76

Analog Inputs

H3-02



0411

Terminal A1 Gain Setting
Terminal A1 Gain

Sets the speed command when 10 V is input, as a percentage of the
maximum output frequency (E1-04).

0.0 ~

1000.0 %

100.0 % Programming

85

H3-03



0412

Terminal A1 Bias Setting
Terminal A1 Bias

Sets the speed command when 0 V is input, as a percentage of the
maximum output frequency (E1-04).

–100.0 ~

+100.0 %

0.0 %

Programming

85

H3-08

0417

Terminal A2 Signal
Level Selection
Term A2 Signal

Selects the signal level of Terminal A2.
0: 0 - 10 Vdc (switch S1-2 must be in the off position)
2: 4 - 20 mA (switch S1-2 must be in the on position)
3: 0- 20 mA

0 or 2

2

Programming

87

H3-09

0418

Aux Terminal Function
Selection
Terminal A2 Sel

Selects what effect the aux terminal has on the drive.
0: Frequency Bias - 0 - 100 % bias
2: Aux Reference
B: PI Feedback
D: Frequency Bias 2 - 0 - 100 % bias
E: Motor Temperature - See parameters L1-03 & L1-04
16: PI Differential
1F: Not Used

0 ~ 1F

B

Programming

88

H3-10



0419

Terminal A2 Gain Setting
Terminal A2 Gain

Sets the percentage when 10 V (20 mA) is input.

0.0 ~

1000.0 %

100.0 % Programming

90

H3-11



041A

Terminal A2 Bias Setting
Terminal A2 Bias

Sets the percentage when 0 V (4 mA) is input.

–100.0 ~

+100.0 %

0.0 %

Programming

91

H3-12

041B

Analog Input Filter Time
Constant Filter Avg Time
Analog Input Fil Tim

Used to “smooth” out erratic or noisy analog input signals.

0.00 ~

2.00 s

0.30 s

Programming

92

H3-13

041C

Master Frequency
Reference
Terminal Sel TA1/A2
Select

Determines which terminal will be the main reference source.
0: Main Fref TA1 - Terminal TA1 is the main speed command and
Terminal TA2 is the Aux speed command.
1: Main Fref TA2 - Terminal TA2 is the main speed command and
Terminal TA1 is the Aux speed command. Only effective when H3-09
is set to 2 “Aux Reference”.

0 ~ 1

0

Programming

92



Denotes that parameter can be changed when the drive is running.

Analog Outputs

H4-01

041D

Terminal FM Monitor
Selection
Terminal FM Sel

Selects which monitor will be output on Terminals FM and AC.
1: Frequency Ref (100 % = max. output frequency)
2: Output Freq (100 % = max. output frequency)
3: Output Current (100 % = drive rated current)
6: Output Voltage (100 % = 230 V or 100 % = 460 V)
7: DC Bus Voltage (100 % = 400 V or 100 % = 800 V)
8: Output kWatts (100 % = drive rated power)
15: Term A1 Level
16: Term A2 Level
18: Mot SEC Current (100 % = Motor rated secondary current)
20: SFS Output (100 % = max. output frequency)
24: PI Feedback
31: Not Used
36: PI Input
37: PI Output (100% = max. output frequency)
38: PI Set-point

Note:

100% = 10 V DC output x FM gain setting (H4-02).

1 ~ 38

<0032>

2

Programming

93

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

No.