beautypg.com

Procedure for setting up communication, Related parameters – Yaskawa iQpump Controller Programming Manual User Manual

Page 98

background image

98

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

Important:

• Separate the communication cables from the main circuit cables and control circuit wiring.
• Use shielded cables for the communication cable, and use proper shield clamps.
• When using RS-485 2 Wire communication, connect S+ to R+, and S- to R-, on the control circuit terminal board. See

Figure 88.

.

• Terminate shield at one end only.

Figure 1.89

Figure 88.

Procedure for Setting Up Communication

Use the following procedure to perform communication with the PLC.

1. Turn OFF the input power to the iQpump drive and connect the communication cable between the PLC and the drive.
2. Turn ON the input power to the drive.
3. Set the required communication parameters (H5-01 ~ H5-09) using the Digital Operator.
4. Turn OFF the input power to the drive, and check that the Digital Operator display has completely faded.
5. Turn ON the input power to the iQpump drive once again.
6. Perform communication with the PLC.

Related Parameters

The following parameters need to be set correctly to insure proper operation of the iQpump drive when using MEMOBUS / Modbus
communication.

Table 35 Serial Communication Related Parameters

Parameter

No.

Addr. Hex

Parameter Name

Digital Operator

Display

Description

Setting

Range

Factory

Setting

Menu

Location

Page

Number

b1-01

0108

Frequency Reference
Selection
Reference Source

Selects the speed command (frequency reference) input source.
0: Operator - Digital preset speed d1-01
1: Terminals - Analog Input Terminal A1 (or Terminal A2 see
parameter H3-13)
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 ~ 3

0

Pump Quick

Setup

260

b1-02

0181

Run Command
Selection
Run Source

Selects the run command input source.
0: Operator - “Hand” and “Off” keys on digital operator
1: Terminals - Contact Closure on Terminal S1
2: Serial Com - RS-485 terminals R+, R-, S+ and S-
3: Option PCB - Option board connected at 2CN

0 ~ 3

1

Pump Quick

Setup

260

H5-01

0425

Drive Node Address
Serial Com Adr

Selects drive station node number (address) for terminals R+, R-, S+,
S-.
Note: An address of “0” disables serial com.
Drive power must be cycled before the changes will take effect.
<0034>
*Range is dependent on P9-25, if P1-01 = 3. <0034>

0 ~ 20*

1F

Programming

272

H5-02

0426

Communication
Speed Selection
Serial Baud Rate

Selects the baud rate for terminals R+, R-, S+ and S-.
0: 1200 Baud
1: 2400 Baud
2: 4800 Baud (APOGEE FLN)
3: 9600 Baud (Metasys N2)
4: 19200 Baud
Note: Drive power must be cycled before the changes will take
effect. <0034>

0 ~ 4

3

Programming

272

H5-03

0427

Communication
Parity Selection
Serial Com Sel

Selects the communication parity for terminals R+, R-, S+ and S-.
0: No Parity
1: Even Parity
2: Odd Parity
Note: Drive power must be cycled before the changes will take
effect. <0034>

0 ~ 2

0

Programming

272