beautypg.com

Yaskawa iQpump Controller Programming Manual User Manual

Page 169

background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

169

Figure 1.120

Figure 124.

Figure 1.121

Figure 125.

Figure 1.122

Figure 126.

The sleep function can be active during the following conditions:

• When P2-20 is set to 0 or 3

<0034>

(disabled), the output frequency must be greater than the Sleep Level (P2-02).

• When P2-20 is greater than P2-02, the output frequency must be greater than Alternative Sleep Activation Level (P2-20). See

Figure 124.

.

• When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level

(P2-20). See

Figure 125.

.

• When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level

(P2-20) and Sleep Level (P2-02). See

Figure 126.

A value of 0 programmed in P2-20 will disable this function.

• P2-01 = 0: Display based on “Hz”

<0034>

P1-06

SLEEP MODE

SLEEP PERMITTED

P2-02

P2-20

P2-03

P1-06

SLEEP PERMITTED

P2-02

P2-20

P2-03

SLEEP MODE

P1-06

SLEEP MODE

SLEEP PERMITTED

P2-02

P2-20

P2-03