YASKAWA TM.iQp.07 iQpump Controller Programming Manual

249

Figure 1.182

Figure 186. Drive Requests for a New Lead Drive using Feedback and Output Frequency (P9-08 = 2)

Figure 1.183

Figure 187. Drive Requests for a De-Stage using Output Frequency (P9-12 = 0)

Output Frequency

PID Active

Add Pump Level P9-09

Add Delay Time

P9-11

Add Delay Time

P9-11

PumpNet Status1 U1-55 bit 4:

Requesting for Staging (next lead)

PumpNet Control1 U1-59 bit 1:

Run as Lag Drive

PumpNet Control1 U1-59 bit 2:

Run as Lead Drive

Set-Point

Feedback

Add Pump Delta

P9-10

Set-Point

Feedback

Output Frequency

Remove Pump Level P9-13

Remove Delay

Time P9-15

Remove Delay

Time P9-15

PumpNet Status1 U1-55 bit 5:

esting for De-staging (previous lead)

PumpNet Control1 U1-59 bit 1:

Run as Lag Drive

PumpNet Control1 U1-59 bit 2:

Run as Lead Drive

Drive ramps down to
zero speed and gets
added back to the
ready-to-run list