B4 delay timers – Yaskawa iQpump Controller Programming Manual User Manual
Page 31

YASKAWA TM.iQp.07 iQpump Controller Programming Manual
31
b4 Delay Timers
The iQpump drive has an internal timer function that operates independently from the drive. A digital input must be programmed to be a
timer start input by setting H1-0x = 18. A digital output must be programmed as a timer output by setting H2-0x = 12. (Not to be
confused with the “Wait to Run Time” in b1-11.)
◆
b4-01 Timer Function ON-Delay Time
Setting Range:
0.0 ~ 3000.0 s
Factory Default: 0.0 s
The timer start input (H1-0x = 18) must be held on for at least the time specified in parameter b4-01 before the digital output programmed
as the timer output will close. See
for timing details.
◆
b4-02 Timer Function OFF-Delay Time
Setting Range:
0.0 ~ 3000.0 s
Factory Default: 0.0 s
The timer start input (H1-0x = 18) must be held off for at least the time specified by b4-02 before the digital output programmed as the
timer output will open. See
for timing details.
Figure 1.25
Figure 25. Timing Diagram of Timer Function
Multi-function Contact
Input: Timer Function
Multi-function Contact
Output: Timer Function
b4-01
b4-01
b4-02
ON (CLOSED)
OFF (OPEN)
ON (CLOSED
OFF (OPEN)
b4-02