MEMOBUS / Modbus Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data.
■
Reference Data
The reference data table is shown below. Reference data can be read and written to.
Table 37 Reference Data
Register Hex
Contents
0000
Reserved
0001
Sequence Control
Bit 0
Run Forward 1: Run 0: Stop
Bit 1
Run Reverse 1: Run 0: Stop
Bit 2
External fault1: Fault (EFO)
Bit 3
Fault reset1: Reset command
Bit 4
ComNet
Bit 5
ComCtrl
Bit 6
Multi-function digital input command 3
Bit 7
Multi-function digital input command 4
Bit 8
Multi-function digital input command 5
Bit 9
Multi-function digital input command 6
Bit A
Multi-function digital input command 7
Bits B ~ F
Not used
0002
Frequency reference (Set units using parameter o1-03)
0003 ~ 0005
Not used
0006
PI Setpoint
0007
Analog output 1 setting (-11 V = 726 ~ 11 V = 726)
→ 10 V = 660
0008
Analog output 2 setting (-11 V = 726 ~ 11 V = 726)
→ 10 V = 660
0009
Multi-function contact output setting
Bit 0
Digital output 1 (Terminal M1-M2) 1: ON 0: OFF
Bit 1
Digital output 2 (Terminal M3-M4) 1: ON 0: OFF
Bit 2
Not Used
Bits 3 ~ 5
Not used
Bit 6
Set fault contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF
Bit 7
Fault contact (terminal MA-MC) 1: ON 0: OFF
Bits 8 ~ F
Not used
000A ~ 000E
Not used
000F
Reference selection settings
Bit 0
Not used
Bit 1
Input PI Setpoint 1: Enabled 0: Disabled
Bits 3 ~ B
Not used
C
Broadcast data terminal S5 input 1: Enabled 0: Disabled
D
Broadcast data terminal S6 input 1: Enabled 0: Disabled
E
Broadcast data terminal S7 input 1: Enabled 0: Disabled
F
Not used
Note: Write 0 to all unused bits. Also, do not write data to reserved registers.