beautypg.com

Memobus / modbus data tables, Reference data – Yaskawa iQpump Controller Programming Manual User Manual

Page 103

background image

YASKAWA TM.iQp.07 iQpump Controller Programming Manual

103

MEMOBUS / Modbus Data Tables

The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data.

Reference Data

The reference data table is shown below. Reference data can be read and written to.

Table 37 Reference Data

Register Hex

Contents

0000

Reserved

0001

Sequence Control

Bit 0

Run Forward 1: Run 0: Stop

Bit 1

Run Reverse 1: Run 0: Stop

Bit 2

External fault1: Fault (EFO)

Bit 3

Fault reset1: Reset command

Bit 4

ComNet

Bit 5

ComCtrl

Bit 6

Multi-function digital input command 3

Bit 7

Multi-function digital input command 4

Bit 8

Multi-function digital input command 5

Bit 9

Multi-function digital input command 6

Bit A

Multi-function digital input command 7

Bits B ~ F

Not used

0002

Frequency reference (Set units using parameter o1-03)

0003 ~ 0005

Not used

0006

PI Setpoint

0007

Analog output 1 setting (-11 V = 726 ~ 11 V = 726)

→ 10 V = 660

0008

Analog output 2 setting (-11 V = 726 ~ 11 V = 726)

→ 10 V = 660

0009

Multi-function contact output setting

Bit 0

Digital output 1 (Terminal M1-M2) 1: ON 0: OFF

Bit 1

Digital output 2 (Terminal M3-M4) 1: ON 0: OFF

Bit 2

Not Used

Bits 3 ~ 5

Not used

Bit 6

Set fault contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF

Bit 7

Fault contact (terminal MA-MC) 1: ON 0: OFF

Bits 8 ~ F

Not used

000A ~ 000E

Not used

000F

Reference selection settings

Bit 0

Not used

Bit 1

Input PI Setpoint 1: Enabled 0: Disabled

Bits 3 ~ B

Not used

C

Broadcast data terminal S5 input 1: Enabled 0: Disabled

D

Broadcast data terminal S6 input 1: Enabled 0: Disabled

E

Broadcast data terminal S7 input 1: Enabled 0: Disabled

F

Not used

Note: Write 0 to all unused bits. Also, do not write data to reserved registers.