YASKAWA TM.iQp.07 iQpump Controller Programming Manual

39

Figure 1.30

Figure 30. Loss of PI Feedback Feature

b5-17 PI Accel / Decel Time

Setting Range:

0.0 ~ 25.5 s

Factory Default: 0.0 s

This is a soft start function that is applied to the PI Setpoint analog input. Instead of having nearly instantaneous changes in signal levels,
there is a programmed ramp applied to level changes. When changing setpoints the error can be limited by gradually ramping the setpoint
through the use of parameter b5-17.

b5-32 Integrator Ramp Limit

<0034>

The Integrator Ramp Limit provides a way to tune the PI loop so that it is less reactive to sudden spikes and dips in the feedback signal.
Sometimes in a pressure regulated system with a very long piping system, pressure waves can develop which without this feature, can
cause instability in the PI controller.

This feature only applies to the drive’s standard PI Loop. It will not be applied to the PI Loop associated with water level control (Well
Draw Down Control).

Function Description

<0034>

Integrator Ramp Limit.

When the Integrator Ramp Limit is enabled, the PI Integrator is limited to +/- the b5-32 value of the soft starter output (output frequency
without slip compensation). A b5-32 setting of zero disables this feature and the integrator is allowed to operate normally.

Table 14 Related Parameter

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location

b5-32

85F

Integrator Ramp Limit
Int Ramp Lim

When set to a value greater than zero, the PI Integrator is forced to be
within +/- this amount of the soft starter output

0.0 ~

10.0 Hz

0.0 Hz

Programming

Measured
Feedback

T

t

Feedback

Loss Output

T

b5-13

T = b5-14

Feedback

Loss Digital Output

ON (CLOSED)

OFF (OPEN)

TIME