beautypg.com

B5-03 integral time setting, B5-04 integral limit setting, B5-06 pi output limit – Yaskawa iQpump Controller Programming Manual User Manual

Page 36: B5-07 pi offset adjustment

background image

36

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

b5-03 Integral Time Setting

Setting Range:

0.0 ~ 360.0 s

Factory Default: 3.0 s

The Integral factor of PI functionality is a time-based gain that can be used to eliminate the error (difference between the setpoint and
feedback at steady state). The smaller the Integral Time set into b5-03, the more aggressive the Integral factor will be. To turn off the
Integral Time, set b5-03 = 0.00.

Figure 1.29

Figure 29. PI Feedback Response Characteristics

b5-04 Integral Limit Setting

Setting Range:

0.0 ~ 100.0%

Factory Default: 100.0%

On some applications, especially those with rapidly varying loads, the output of the PI function may have large oscillations. To suppress
these oscillations, a limit can be applied to the integral factor by programming b5-04.

b5-06 PI Output Limit

Setting Range:

0.0 ~ 100.0%

Factory Default: 100.0%

Places a cap on the output of the PI function. Limiting the PI function may help to prevent large overshoots in the drive’s response to error
(the difference between the setpoint and the feedback).

b5-07 PI Offset Adjustment

Setting Range:

-100.0% ~ +100.0%

Factory Default: 0.0%

The PI Offset Adjustment parameter has two different uses. Parameter b5-07 serves different functions depending on whether it is used
on a standard PI loop or a Differential PI loop.

Parameter b5-07 causes an offset to be applied to the output of the PI function in a non-Differential PI loop. Every time the PI output is
updated, the offset (b5-07) is summed with the PI output. This can be used to artificially kick-start a slow starting PI loop.

If the iQpump drive is configured for Differential PI Regulation (H3-09 = “16: PI differential”), then this parameter is the target setpoint
for the differential to be maintained between the signal measured on analog input A1 and the signal measured on analog input A2.

Zero

offset with

Integral Action

No Integral

With Integral

Me

asu

red

Fe

ed

back

Me

asur

ed

Fe

edb

ack

Setpoint

Offset

Setpoint

Feedback

Feedback

TIME

TIME