Yaskawa iQpump Controller Programming Manual User Manual
Page 263

YASKAWA TM.iQp.07 iQpump Controller Programming Manual
263
C1-09
0208
Fast Stop Time
Fast Stop Time
Sets the time to decelerate from maximum frequency to zero for the
“Fast Stop” function.
0.0 ~
6000.0 s
10.0 s
Programming
C1-11
020A
Accel / Decel Switch
Frequency
Acc/Dec SW Freq
Sets the frequency for automatic switching of accel / decel times.
Fout < C1-11: Accel / Decel Time 2
Fout > = C1-11: Accel / Decel Time 1
Multi-function input “Multi-Acc / Dec 1" has priority over C1-11.
0.0 ~
200.0 Hz
0.0 Hz
Programming
S-Curve Accel/Decel
C2-01
020B
S-Curve Characteristic at
Accel Start
SCrv Acc @ Star
t
0.00 ~
2.50 s
0.20 s
Programming
C2-02
020C
S-Curve Characteristic at
Accel End
SCrv Acc @ End
0.00 ~
2.50 s
0.20 s
Programming
Torque Compensation
C4-01
0215
Torque Compensation
Gain
Torq Comp Gain
This parameter helps to produce better starting torque. It determines
the amount of torque or voltage boost based upon motor current and
motor resistance.
0.00 ~ 2.50
1.00
Programming
C4-02
0216
Torque Compensation
Primary Delay Time
Torq Comp Time
This parameter adjusts a filter on the output of the torque compensation
function. Increase to add torque stability, decrease to improve torque
response.
0 ~
10000 ms
200 ms Programming
Denotes that parameter can be changed when the drive is running.
Carrier Frequency
C6-02
0224
Carrier Frequency
Selection
CarrierFreq Sel
Carrier frequency sets the number of pulses per second of the output
voltage waveform.
1: 2.0 kHz
2: 5.1 kHz
3: 8.0 or 7.0* kHz
F: Program (Determined by the setting of C6-03)
* when an option card is installed
1 ~ F
kVA
Dependent
Programming
C6-03
0225
Carrier Frequency Upper
Limit
CarrierFreq Max
Maximum carrier frequency allowed when C6-02 = F.
0.4 ~
15.0 kHz
kVA
Dependent
Programming
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
Time
Run
command
Output frequency
ON
C2-02
C2-01
OFF
S-curve is used to further soften the starting ramp.
The longer the S-curve time, the softer the starting
ramp.