Yaskawa iQpump Controller Programming Manual User Manual
Page 207

YASKAWA TM.iQp.07 iQpump Controller Programming Manual
207
Figure 1.157
Figure 161. Lube Pump Enabled with Anti-Jam Enabled
Table 84 Parameters
Table 85 Multi-Function Output Setting
<0034>
Table 86 Message
<0034>
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Range
Default
Menu
Location
P4-23
836
Lube Pump Delay Timer
Lube Pump Time
Sets the amount of time the drive's output will be delayed and the
Lube Pump digital output (H2-0x = 55) will be energized. A setting
of zero will disable this feature.
0.0 ~
300.0 s
0.0
Programming
Denotes that parameter can be changed when the drive is running.
Setting
Description
55
Lube Pump
Indicates that sufficient / insufficient pressure is present on the inlet to the pump. Used mainly for pressure booster stations.
Setting
Description
Lube Pump Running
The drive is delaying the start of the motor and the Lube Pump digital output is energized.
Run
Command
Output
Frequency
Anti-Jam
Alarm
Output
Current
P7-04
PwrL Baseblock t
L2-03
P7-04
L2-03
P7-04
L2-03
P7-04
L2-03
L2-03
P7-04
P7-04
AJF
Anti-Jam Fault
Anti-Jam Det. Current
P7-03
C1
-0
1
*
C1
-01*
* Acceleration rate will be un -modified by the anti -jam function. If the
Trust Bearing feature is enabled , the acceleration rate will be P 4-04.
P7-02 = 3
A-J Cycle Count
Cycle
1
Cycle
2
Cycle
3