P6-04 Low Flow Level
Setting Range:
0.0 ~ 6000.0 (*n1)
Factory Default: 0.0
(*n1) Displayed units are determined by parameter P6-02.
◆
P6-05 Low Flow Detection Delay Time When Already Running
Setting Range:
0 ~ 6000 sec
Factory Default: 10
Refer to parameter P6-05 in Appendix A for description details.
◆
P6-06 Low Flow Detection Wait Time At Start
Setting Range:
0.00 ~ 3600.0 min
Factory Default: 0.00
Refer to parameter P6-06 in Appendix A for description details.
◆
P6-07 Low Flow Select
◆
P6-08 Low Flow Auto-Restart Time
Setting Range:
0.1 ~ 6000.0 min
Factory Default: 3.0 min
Refer to parameter P6-08in Appendix A for description details.
◆
P6-09 Accumulation Level Fine
Setting Range:
0.0 ~ 999.0 gal
Factory Default: 0.00
Refer to parameter P6-09 in Appendix A for description details.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Range
Default
Menu
Location
P6-04
843
Low Flow Level
Low Flow Level
If the drive is running, and the flow goes below this level for more
than the P6-05 time, a Low Flow fault or alarm will occur. A setting
of 0 disables the low flow detection. If P1-01 = 3, a LOWFL fault
will stop all drives running on the network.
0.0 ~
6000.0
(*n1)
0.0
Programming
Denotes that parameter can be changed when the drive is running.
(*n1) Displayed units are determined by parameter P6-02.
Setting
Description
0
No Display
1
Alarm Only
2
Fault
3
Auto-Restart (time set by P6-08)