H2 digital outputs, Terminal function selections – Yaskawa iQpump Controller Programming Manual User Manual
Page 76

76
YASKAWA
TM.iQp.07 iQpump Controller Programming Manual
H2 Digital Outputs
◆
Terminal Function Selections
Setting Range:
0 ~ 57
Factory Defaults: H2-01 = “40: Pump 2 Control”
H2-02 = “41: Pump 3 Control”
The iQpump drive has two multi-function outputs. By programming parameters H2-01 and H2-02, the user can assign specific functions
to each output. Below is a table with a complete list of all of the digital output functions. Because the iQpump drive is a dedicated pump
controller, the digital outputs described in this section only relate to the pump specific functions. Following the table is a more detailed
description of each of the pump related functions.
Table 29 Digital Output Functions
Table 30 Parameters
<0034>
Parameter No.
Parameter Name
H2-01
Terminal M1-M2 Function Selection
H2-02
Terminal M3-M4 Function Selection
Parameter setting
Function
Parameter setting
Function
0
During Run1
3B
Run from Serial Com
1
Zero Speed
3D
Cooling Fan Err
2
FREF / FOUT Agree 1
40
Pump 2 Control
3
FREF / Set Agree 1
41
Pump 3 Control
4
Frequency Detect 1
42
Pump Fault
5
Frequency Detect 2
43
Mot 2 Alternate
6
Drive Ready
44
Sleep Active
7
DC Bus Undervoltage
45
Start Lvl Delay
8
Baseblock 1
46
Thrust Bearing
9
Option Reference
47
Pre-charge
A
Remote Operation
48
High Feedback
B
Torque Detect 1 N.O.
49
Low Feedback
C
Loss of Reference
4A
Transducer Loss
E
Fault
4B
Setpoint Not Met
F
Terminal Not Used
4C
Loss of Prime
10
Minor Fault
4D
Thermostat Fault
11
Reset Cmd Active
4E
Low Flow
12
Timer Output
4F
Accum Level
17
Torque Detect 1 N.C.
50
Utility Delay
1A
Reverse Direction
51
Run / Stop-Stop
1E
Restart Enabled
52
Run / Stop-Finish
1F
Overload (OL1)
53
Anti-Jam / De-Scale
20
OH Pre-alarm
54
During Run 2
38
Drive Enable
55
Lube Pump
39
Drive Waiting
56
High Flow
3A
Frequency Reduced, OH
57
Low Water Level
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
H2-01
40B
Terminal M1-M2 Function
Selection
Terminal M1-M2 Sel
Selects the functionality of the M1-M2 digital output contacts.
0 ~ 57
40
Programming
H2-02
40C
Terminal M3-M4 Function
Selection
Terminal M3-M4 Sel
Selects the functionality of the M3-M4 digital output contacts.
0 ~ 57
40
Programming