B1-03 stopping method, 00hz – Yaskawa iQpump Controller Programming Manual User Manual
Page 21

YASKAWA TM.iQp.07 iQpump Controller Programming Manual
21
Table 1 Related Parameters
<0034>
Table 2 Digital Operator Display
Table 3 Fault
<0034>
Table 4 Message
<0034>
Table 5 Multi-Function Output Setting
<0034>
◆
b1-03 Stopping Method
There are four methods of stopping the iQpump drive when the Run command is removed.
Parameter
No.
Addr. Hex
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
P4-18
831
Run / Stop Control Run Time
R-S Run Time
This parameter sets the amount of time the drive will run for when
the Run / Stop Control is enabled. It will also set the “timed” run time
when enabled (b1-02 = 5).
0.0 ~
6000.0 min
0.0 min Programming
P4-19
832
Run / Stop Control Stop Time
R-S Stop Time
This parameter sets the amount of time the drive will stop for when
the Run / Stop Control is enabled.
0.0 ~
6000.0 min
0.0 min Programming
P4-20
833
Run / Stop Control Cycles
R-S Cycle Count
This parameter determines how many Run / Stop Cycles the drive
will execute before staying stopped.
0 ~ 1000
0
Programming
Denotes that parameter can be changed when the drive is running.
Description
Operator Display
When the Run / Stop function is enabled, the display will change as shown.
The Run / Stop function is enabled by setting parameters P4-18, P4-19 and P4-20
to values greater than zero.
Fault Display
Description
Cause
Countermeasures
oPE15
Run / Stp-
Run / Stop or Timed Run enabled in
multiplex mode.
Run / Stop Control has been enabled when in multiplex mode.
(P1-01 > 0, P4-18 > 0, P4-19 > 0 and P4-20 > 0).
OR
Timed Run Control has been enabled when in multiplex mode.
(P1-01 > 0 and b1-02 = 5).
Reprogram P1-01, P4-18 ~ P4-20,
or b1-02.
Fault Display
Description
Cause
Countermeasures
Run / Stop Finished Run / Stop Cycles have completed.
The number of Run / Stop Cycles since the last HAND command
has completed.
Press “Off” to clear the message.
Setting
Description
51
Run / Stop - Stop
Closed: Drive is stopped due to the Run / Stop control (P4-18 and P4-19) OR
Closed: Drive is stopped because the Run / Stop cycles have completed (P4-20).
52
Run / Stop - Finish
Closed: Drive is stopped because the Run / Stop cycles have completed (P4-20).
Setting
Description
0
Ramp to Stop (
factory default
)
1
Coast to Stop
2
DC Injection to Stop
3
Coast w / Timer
Run/Stop Control
40.00Hz
0.00 Hz
0.0 PSI