YASKAWA TM.iQp.07 iQpump Controller Programming Manual

159

Figure 1.115

Figure 119. Sleep Boost: Feedback does not reach boosted setpoint

Table 65 Related Parameters

<0034>

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P1-04



603

Start Level
Start Level

Drive starts when the feedback level drops below the start level for a
time specified in P1-05. This level also specifies the wake up level
when the drive is in Sleep Mode.
If set to a negative value, the feedback level must drop by this amount
below the setpoint.
Note:

When PID operates in the reverse mode, the feedback value

has to rise above the start level for the time programmed in P1-05 for
the system to start. A value of 0 disables this function.
If P1-01 = 3, the function is active only on the first drive in the
network.

- 999.9 ~

999.9

(system

units

P1-02)

0.0

(system

units

P1-02)

Pump Quick

Setup

P1-12



107

Not Maintaining Set Point Time
Not Maint SP Tm

Delay time before a Not Maintaining Setpoint fault occurs. Pump
protection criteria specified in P1-11 must be met for the drive to
fault. On fault the drive will coast to a stop.

Setting P1-12 = 0 disables the Not Maintaining Setpoint fault.

0 ~ 3600 s

60 s

Programming

P2-01

60A

Sleep Level Type
Sleep Lvl Type

Select sleep type:
0 = Output Frequency
1 = Output Current
2 = Feedback
3 = Output Speed (rpm)
4 = Low Flow (Term A1 - Flow Meter Required)
Note:

Feedback depends on PID direction operation.

Display “Sleep” Alarm when active.

0 ~ 4

0

Programming

P2-02



Sleep Level
Sleep Level

Sleep activates when selected level (P2-01) reaches programmed
sleep level for time specified in P2-03. Level Type is determined by
P2-01.
A value of 0 disables this function. This function is only active during
running while operating in auto mode.

Display Units for Sleep Level P2-02:

P2-01 = 0, => “Hz”
P2-01 = 1, => “A”
P2-01 = 2, => P1-02 Selection
P2-01 = 3, => “rpm”
P2-01 = 4, => P6-02 Selection

Note:

When P2-01 is set for a value of 2 display units will be

dependent on P1-02 setting. If P2-02 = 0, pump will sleep at
minimum speed.

0 ~ 6000.0

0.0

Programming

P2-03



Sleep Delay Time
Sleep Delay Time

Delay time before drive enters sleep mode when criteria is met as
defined by parameter P2-02.

0 ~ 3600 s

5 s

Programming

Run Cmd.

PI Setpoint

Output

Frequency

P2-03

Sleep Delay Time

Sleep Boost Lvl (P2-21)

PI

Feedback

PI Setpoint

Start Level (P1-04)

Sleep Boost Lvl (P2-21)

P2-22

Sleep Boost Time

Sleep

Active

P1-05

S-Lvl Delay Time

P2-02

Sleep Level