Broadcast Data
The following table shows the broadcast data. Broadcast Data Can Be Written (function Code 06 / 10) only.
Table 39 Broadcast Data
■
Enter Command
When writing parameters to the iQpump drive from the PLC using MEMOBUS / Modbus communication, the parameters are
temporarily stored in the constant data area in the drive. To enable these parameters in the parameter data area, use the Enter command.
There are two types of Enter commands:
1. Enter commands that enable parameter data in RAM
2. Enter commands that write data to EEPROM (non-volatile memory) in the iQpump drive at the same time as enabling data in RAM.
The following table shows the Enter command data. Enter command data can only be written.
The Enter command is enabled by writing 0 to register number 0900 or 0901.
Table 40 Enter Command
Important: The maximum number of times the EEPROM can be written using the iQpump drive is 100,000. Do not frequently execute
Enter commands (0900) written to EEPROM.
The Enter command registers are write-only. Consequently, if reading these registers, the register address will become invalid (Error
code: 02).
Register Hex
Contents
0001
Operation signal
Bit 0
Run forward 1: Run 0: Stop
Bit 1
Reverse operation command 1: Run 0: Stop
Bits 2 and 3
Not used
Bit 4
External error (1: Fault set using H1-01)
Bit 5
Error (Fault 1: Reset commandset using H1-02)
Bits 6 ~ B
Not used
Bit C
Multi-function digital input terminal S5 input
Bit D
Multi-function digital input terminal S6 input
Bit E
Multi-function digital input terminal S7 input
Bit F
Not used.
0002
Frequency reference
30000 / 100%
Note: Bit signals not defined in the broadcast operation signals use local node data signals continuously.
Register Hex
Contents
0900
Write parameter data to EEPROM
0910
Parameter data is not written to EEPROM, but refreshed in RAM only.