Warning – Yaskawa iQpump Controller Programming Manual User Manual
Page 285
YASKAWA TM.iQp.07 iQpump Controller Programming Manual
285
P4-08
<0032>
011C
Protection Fault Auto
Restart Enable
Prot Flt Restrt
Setting to enable / disable Auto Restart for the following iQpump
protection faults (N = disable / Y = enable):
SP: Not Maintaining SetPoint (P1-11)
LOP: Loss of Prime (P1-16)
POC: Pump Over Cycling (P2-08))
0: POC = N LOP = N SP = N
1: POC = N LOP = N SP = Y
2: POC = N LOP = Y SP = N
3: POC = N LOP = Y SP = Y
4: POC = Y LOP = N SP = N
5: POC = Y LOP = N SP = Y
6: POC = Y LOP = Y SP = N
7: POC = Y LOP = Y SP = Y
Note:
Parameter L5-01 needs to be set to “1” and program L5-03 needs
to be set to the applicable time.
0 ~ 7
0
Programming
P4-09
<0032>
011D
Loss of Prime Maximum
Restart Time After Fault
LOP Max Rstrt T
If the restart fails (or is not attempted due to a continuing fault
condition) the drive waits this many minutes before attempting another
restart.
Note:
This parameter will take the place of L5-03 during a Loss of
Prime Fault restart attempt.
0.2 ~
6000.0 min
0.2 min Programming
P4-10
011E
Auto Mode Operator Run
Power Down Storage.
AMO PwDn-Storage
Stores the run status in the Auto mode when operating from digital
operator (b1-02 = 0).
0: Disabled.
1: Enabled.
0 ~ 1
0
Pump Quick
Setup
When the drive is powered down while running, then upon power-up it will
automatically initiate an internal run command.
P4-11
<0034>
82A
Utility Start Delay
Utility Delay
Sets the amount of time the drive will delay starting if a run command
is present at power up.
A setting of 0.0 disables this function.
If P1-01 = 3, the drive is unavailable to the network (Pump Off
Network) when the function is active.
<0034>
0.0 ~
1000.0 min 0.2 min Programming
P4-12
<0034>
82B
Pre-charge Frequency 2
Pre-charge Freq2
Frequency reference used when Pre-charge 2 function is active.
A value of 0.00 disables this function.
0.00 ~
120.00 Hz
0.00 Hz Programming
P4-13
<0034>
82C
Pre-charge Time 2
Pre-charge Time2
Time at which the drive will spend at the Pre-charge Frequency 2
(P4-12) speed during pre-charge.
A value of 0.0 disables this function.
0 ~
3600.0 min 0.0 min Programming
P4-14
<0034>
82D
Two Motor Alternation
Selection
Mot 2 Alternate
Selects if the alternation feature is enabled.
0: Disabled
1: Enabled
2: Motor 1 Only
3: Motor 2 Only
0 ~ 3
0
Programming
P4-15
<0034>
82E
Alternation Operation
Selection
Alternation Oper
Selects the drive behavior when the internal alternation timer expires.
0: Wait For Stop
1: Immediate
0 ~ 1
0
Programming
P4-16
<0034>
82F
Alternation Time
Alternation Time
Selects the amount of time each motor will run before the drive
switches to the other motor.
1.0 ~
100.0 hr
24.0 hr
Programming
P4-17
<0034>
830
Dual Zone PID Feedback
Bandwidth Range
Dual Zone Range
Determines the detection bandwidth for the dual zone PI control.
0 ~ 6000.0
(system
units
P1-02)
10.0
(system
units
P1-02)
Programming
P4-18
<0034>
831
Run-Stop Control Run
Time
R-S Run Time
This parameter sets the amount of time the drive will run for when the
run-stop control is enabled. It will also set the “timed” run time when
enabled (b1-02 = 5).
0.0 ~
6000.0 min 0.0 min Programming
P4-19
<0034>
832
Run-Stop Control Stop
Time
R-S Stop Time
This parameter sets the amount of time the drive will stop for when the
run-stop control is enabled.
0.0 ~
6000.0 min 0.0 min Programming
P4-20
<0034>
833
Run-Stop Control Cycles
R-S Cycle Count
This parameter determines how many run-stop cycles the drive will
execute before staying stopped.
0 ~ 1000
0
Programming
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.
WARNING