YASKAWA TM.iQp.07 iQpump Controller Programming Manual

257

Figure 1.192

Figure 196. P9-20, P9-21 and P9-24 Interaction Example

Table 122 Parameters

MEMOBUS / Modbus Interaction with other iQpump Functions

Function Description

<0034>

All functions will work as before when P1-01

3. The functions listed below will behave slightly different when P1-01 = 3.

Start Level: Active on the first pump in the network. Drives that are in the process of Alternation will not undergo this process.
Sleep: Active when the drive is the only drive running on the network.
Over-cycle Protection: Active when the drive is the only drive running on the network.
No-Flow Detection: Active on the lead drive. When No-Flow is confirmed, the lead-drive is de-staged, or if it is the only drive left, it

goes to sleep.

Pre-charge: Active only on the first drive to run in the network.
Low City Pressure: Active on any drive in the network. An alarm condition will cause other drives in the network to stop running and

show a “Net Pump Err” message.

Utility Delay: When this function is active the drive is unavailable to the iQpump MEMOBUS / Modbus Network and will force the

U1-01 text to show “Pump Off Network”.

Parameter

No.

Addr.

Hex

Parameter Name

Digital Operator Display

Description

Range

Default

Menu

Location

P9-20

0893

Allow Network Run
Allow Net Run

Specifies when a network run command is allowed:
0: Always
1: First / Alternation
2: First Only
3: Alternation Only

0 ~ 3

0

Programming

P9-21



0894

Run Priority
Run Priority

Sets the Lead Drive selection priority overriding the P9-01 selection.
If multiple drives have the lowest P9-21 value, then P9-01 determines
which drive becomes the Lead.

1 ~ 16

8

Programming

P9-24



0897

Lead Swap @ Sleep
Lead Swap @ Sleep

When the Lead DRive has been in Sleep for this amount of time and
there is another drive available with a lower P9-21, then this drive
will request for a swap.
A setting of 0 disables this function.

0 ~ 7200 s

0 s

Programming



Denotes that parameter can be changed when the drive is running.

Drive 1

Drive 2

Drive 3

U1-13 = 21H
P9-05 = 0 (Fixed Speed)
P9-20 = 0 (Always)
P9-21 = 6
P9-24 = 120s

U1-13 = 30H
P9-05 = 2 (Turn Off )
P9-20 = 2 (First Drive Only)
P9-21 = 3
P9-24 = 0s

Start-up…

Drive 1 is the

First Pump

P9-01 = 1 (Lowest Run-time)

U1-13 = 4H
P9-05 = 0 (Fixed Speed)
P9-20 = 0 (Always)
P9-21 = 6

PumpNet Control 1 U1-xx bit 1:

Run as Lag Drive

PumpNet Control 1 U1-xx bit 2:

Run as Lead Drive

PumpNet Control 1 U1-xx bit 1:

Run as Lag Drive

PumpNet Control 1 U1-xx bit 2:

Run as Lead Drive

PumpNet Control 1 U1-xx bit 1:

Run as Lag Drive

PumpNet Control 1 U1-xx bit 2:

Run as Lead Drive

-

Sleep

Sleep

When

Drive 3 is

staged,
Drive 1

turns off

Only

Drive 2

is

available

as Next

Lead

Drive 2 is no

longer needed

and gets

de-staged

Drive 3 has

been in Sleep

for 120s and

Lead is switched

back to Drive 1

because of the

P9-21 level

iQpump

iQpump

iQpump