P6-10 accumulation level course, P6-11 accumulation behavior, P6-12 high flow level – Yaskawa iQpump Controller Programming Manual User Manual
Page 218: P6-13 high flow detection delay time

218
YASKAWA
TM.iQp.07 iQpump Controller Programming Manual
◆
P6-10 Accumulation Level Course
Setting Range:
0 ~ 61036 kgl
Factory Default: 0
Refer to parameter P6-10 in Appendix A for description details.
◆
P6-11 Accumulation Behavior
◆
P6-12 High Flow Level
Setting Range:
0.0 ~ 6000.0 (*n1)
Factory Default: 0.0
(*n1) Displayed units are determined by parameter P6-02).
◆
P6-13 High Flow Detection Delay Time
Setting Range:
1 ~ 6000 s
Factory Default: 10
Refer to parameter P6-13 in Appendix A for description details.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Range
Default
Menu
Location
P6-09
848
Accumulation Level Fine
Accum Lvl Fine
Sets the accumulated volume that will trigger the Accum Level
alarm, Accum Level fault, or Accum Level digital output. Total
Accum Level can be calculated as follows: Total Accum Level =
P6-10 x 1000 + P6-09. If P1-01 = 3, an ACCUM fault will stop all
drives running on the network.
0.0 ~ 999.0
gal
0.0
Programming
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Range
Default
Menu
Location
P6-10
849
Accumulation Level Course
Accum Lvl Course
Sets the accumulated volume that will trigger the Accum Level
alarm, Accum Level fault, or Accum Level digital output. Total
Accum Level can be calculated as follows: Total Accum Level = P6-
10 x 1000 + P6-09. If P1-01 = 3, an ACCUM fault will stop all drives
running on the network.
0 ~ 61036
kgl
0
Programming
Denotes that parameter can be changed when the drive is running.
Setting
Description
0
No Display
1
Alarm Only
2
Fault
3
Auto-Restart (time set by P6-08)
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description
Range
Default
Menu
Location
P6-12
48B
High Flow Level
High Flow Level
If the drive is running, and the flow goes above this level for more
than the P6-13 time, a High Flow fault or alarm will occur. A setting
of 0 disables the high flow detection. If P1-01 = 3, a HIFLO fault will
stop all drives running on the network.
0.0 ~
6000.0
(*n1)
0.0
Programming
Denotes that parameter can be changed when the drive is running.
(*n1) Displayed units are determined by parameter P6-02.