Yaskawa iQpump Controller Programming Manual User Manual
Page 293

YASKAWA TM.iQp.07 iQpump Controller Programming Manual
293
U1-92
0722
Pump Status
Pump Status
Display pump running status.
U1-93
723
Total Set-point Compensation
Total SP Comp.
Displays total absolute setpoint compensation.
Resolution 1.
U1-94
724
Motor Speed
Motor Speed
Displays motor speed (rpm).
Used for no-flow detection (P2 Group).
U1-95
725
Flow Rate
Flow Rate
Displays the flow rate, based upon the voltage present on Terminal A1 and parameters P6-01
and P6-02. A two second 1st order filter will be applied to this monitor.
U1-96
72A
Volume Accumulated
(fine)
Volume (fine)
Displays the volume that has been measured by Terminal A1. Total volume can be calculated
as follows: Total Volume = U1-97 x 1000 + U1-96.
Value retained in EEPROM.
U1-97
72B
Volume Accumulated
(course)
Volume (course)
Displays the volume that has been measured by Terminal A1. Total volume can be calculated
as follows: Total Volume = U1-97 x 1000 + U1-96.
Value retained in EEPROM.
U1-98
72C
Water Level
Water Level
Displays the amount of water above the water level sensor.
U1-99
72D
Anti-No-Flow Timer
ANF Timer
When this value reaches the P2-24 setting, the Anti-No-Flow feature begins to reduce the
output frequency.
Parameter No.
Addr.
Hex
Parameter Name Digital
Operator Display
Description
Monitor
0 0 0 0 0 0 0 0
1: Drive (Pump 1)
1: Pump 2 on
1: Pump 3 on
Not used. Always 0.