240

YASKAWA

TM.iQp.07 iQpump Controller Programming Manual

P9-12 Remove Pump Mode

P9-13 Remove Freq Level

Setting Range:

0.0 ~ 120.0 Hz

Factory Default: 40.0 Hz

Refer to parameter P9-23 in Appendix A for description details.

P9-14 Remove Delta Level

Setting Range:

0 ~ 6000.0

Factory Default: 0.0

Refer to parameter P9-24 in Appendix A for description details.

P9-15 Remove Delay Time

Setting Range:

0 ~ 3600 s

Factory Default: 10 s

Refer to parameter P9-15 in Appendix A for description details.

P9-16 Stabilization Time

Setting Range:

0 ~ 3600 s

Factory Default: 3 s

If Stabilize Time P9-16 > 0, then whenever a pump becomes a lag drive, or gets de-staged that disables lead-lag control and pump
protection. It will resume these functions when the timer P9-16 expires, which counts only when the drive becomes a lead drive once
again.

P9-17 Setpoint Modifier

Setting Range:

-6000.0 ~ 6000.0

Factory Default: 0.0

Setpoint Modifier P9-17 is used to increase or decrease the setpoint each time an additional pump is brought online to compensate for
system losses or gains. The drive's setpoint is modified using this calculation:

Pump X: Setpoint + ((X-1)(P9-17))

Thus, if there is only one pump running, the setpoint is not modified.

P9-18 High Feedback Quick De-Stage

Setting Range:

0.0 ~ 100.0%

Factory Default: 90.0%

Refer to parameter P9-18 in Appendix A for description details.

Setting

Description

0

Output Frequency

1

Feedback

2

Feedback + Fout